| Permit Number |
21081271 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-09-24 19:27:42 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. FBC 107 IT APPEARS THAT MORE THAN ONE STRUCTURE IS | | | AFFECTED BY THE PROPOSED WORK. A SEPARATE PERMIT IS | | | REQUIRED FOR EACH STRUCTURE. EMAIL THE PERMIT | | | APPLICATION TO [email protected] IF MORE THAN ONE | | | STRUCTURE IS AFFECTED. IF ONLY ONE STRUCTURE IS | | | INCLUDED IN THE SCOPE OF WORK, REVISE THE SITE PLAN TO | | | CLARIFY. | | | | | | THE PLANS WILL BE STAMPED WITH BOTH PERMIT NUMBERS; NO | | | NEED TO UPLOAD ADDITIONAL PLANS. THE VALUE, HOWEVER, | | | DOES NEED TO BE ASSIGNED TO EACH PERMIT. |
|