| 2021-11-18 16:36:17 | 2ND REVIEW FBC-2017 PLUMBING |
| | PERMIT- 21081267 |
| | 11/18/21 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 6TH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 6TH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE 6TH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 6TH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS FOR THE MAIN POOL- DENIED. FAILED |
| | COMMENTS FROM THE 1ST REVIEW ARE LISTED BELOW WITH |
| | ADDITIONAL NOTES IN CAP LETTERS. |
| | |
| | 1) FAIILED. PLEASE PROVIDE A LIST OF REQUIRED SEPARATE |
| | PERMITS ON THE PLAN INCLUDING- |
| | ON SITE PLUMBING FOR WATER SUPPLY AND WASTE-WATER |
| | DISPOSAL. |
| | BACKFLOW PREVENTER FOR THE WATER SUPPLY TO THE POOL. |
| | AUTO FILL INSTALLATION. |
| | RESTROOM FACILITY AND PLUMBING AND FIXTURE |
| | INSTALLATIONS. |
| | POOL SHOWER AND HOSE BIB PLUMBING AND FIXTURE |
| | INSTALLATIONS. |
| | PAVILION AND EQUIPMENT ENCLOSURE CONSTRUCTION. |
| | POOL FENCE |
| | PAVER DECK |
| | |
| | 5) FAILED. SHEET 1: THE DISCHARGE WATER FROM THE POOL |
| | SHALL NOT DRAIN INTO THE CITY SANITARY SYSTEM- SECTION |
| | 454.1.6.5.15 & SEC. 90-126(5) WPB CODE OF ORDINANCES. |
| | PLEASE REVISE THE PLANS TO SHOW AN APPROVED PLACE OF |
| | DISPOSAL. THE DISCHARGE WATER IS ALSO SHOWN TO BE |
| | DRAINING INTO THE STORM DRAIN SYSTEM IN THE WASTE |
| | DETAIL ON SHEET 6. PLEASE NOTE THAT THE CITY OF WPB |
| | UTILITIES DEPT. PROHIBITS POOL WASTE-WATER FROM |
| | DRAINING INTO THE STORM DRAIN SYSTEM UNLESS THE WATER |
| | HAS BEEN DECHLORINATED. THE ENGINEER OF RECORD SHALL |
| | PROVIDE A PROCEDURE AND EQUIPMENT SPECIFICATIONS. IN |
| | RESPONSE ONE OF THE TWO RESPONSE NARRATIVES INDICATES |
| | ALL WATER TO BE DE-CHLORINATED AND ROUTED TO THE STORM. |
| | THE SECOND NARRATIVE INDICATES A DE-CHLORINATOR HAS |
| | BEEN PROVIDED. |
| | |
| | A) PLEASE SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE |
| | DE-CHLORINATOR. |
| | |
| | B) PLEASE CONTACT THE CHRIS JACKSON, ENVIRONMENTAL |
| | COMPLIANCE SPECIALIST III, PUBLIC UTILITIES DEPARTMENT, |
| | 561-822-2062 OR [email protected] FOR FURTHER |
| | DIRECTION. |
| | |
| | C) PLEASE REMOVE ALL DETAILS AND NOTES FROM THE PLAN |
| | INDICATING POOL WASTE WATER DRAINING INTO THE SANITARY, |
| | AND ADD NOTES TO INDICATE ONLY DE-CHLORINATED WATER TO |
| | DRAIN INTO THE STORM SYSTEM- SEE SHEETS PPP-2, P0-1, |
| | P0-3, P0-6. |
| | |
| | 13) FAILED. SHEET 2: PROVIDE TOTAL DYNAMIC HEAD |
| | CALCULATIONS AND THE PUMP CURVE FROM THE MANUFACTURER- |
| | SECTION 454.1.6.5.4 FBC B. TDH CALCS AND PUMP CURVE NOT |
| | PROVIDED. |
| | |
| | 16) FAILED. SHEETS 4 & 6: PLEASE PROVIDE THE DIMENSIONS |
| | OF THE GUTTERS IN COMPLIANCE WITH SECTION |
| | 454.1.6.5.3.1.1 FBC B. NOT PROVIDED. |
| | |
| | 20) PLEASE SHOW COMPLIANCE WITH THE FOLLOWING CODE |
| | SECTIONS FROM THE FBC EC: |
| | FAILED. C404.9.1 HEATERS. THE ELECTRIC POWER TO ALL |
| | HEATERS SHALL BE CONTROLLED BY A READILY ACCESSIBLE |
| | ON-OFF SWITCH THAT IS AN INTEGRAL PART OF THE HEATER, |
| | MOUNTED ON THE EXTERIOR OF THE HEATER, OR EXTERNAL TO |
| | AND WITHIN 3 FEET (914 MM) OF THE HEATER. OPERATION OF |
| | SUCH SWITCH SHALL NOT CHANGE THE SETTING OF THE HEATER |
| | THERMOSTAT. SUCH SWITCHES SHALL BE IN ADDITION TO A |
| | CIRCUIT BREAKER FOR THE POWER TO THE HEATER. GAS-FIRED |
| | HEATERS SHALL NOT BE EQUIPPED WITH CONTINUOUSLY BURNING |
| | IGNITION PILOTS. HEATER SPECS WERE NOT PROVIDED AND |
| | SWITCH LOCATION NOT SHOWN. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |