| 2021-09-16 15:04:08 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) THERE IS AN INDICATION OF A RAILING HEIGHT OF 38'. |
| | |
| | A RAILING IS FOR STAIRS, A GUARD IS FOR THIS TYPE OF |
| | INSTALLATION. THE GURD HEIGHT IS 42". |
| | |
| | PER NFPA 101 |
| | |
| | 7.2.2.4 GUARDS AND HANDRAILS. |
| | GUARDS ARE TO HELP PREVENT A FALL OVER AN OPEN SIDE OF |
| | A WALKING |
| | SURFACE. HANDRAILS ARE TO HELP ARREST A FALL ON A STAIR |
| | OR RAMP. |
| | |
| | 7.2.2.4.6 GUARD DETAILS. |
| | |
| | 7.2.2.4.6.2 GUARDS SHALL BE NOT LESS THAN 42 IN. (1065 |
| | MM) HIGH, EXCEPT |
| | AS PERMITTED BY ONE OF THE FOLLOWING: |
| | (1) EXISTING GUARDS WITHIN DWELLING UNITS SHALL BE |
| | PERMITTED TO BE NOT |
| | LESS THAN 36 IN. (915 MM) HIGH. |
| | (2) THE REQUIREMENT OF 7.2.2.4.6.2 SHALL NOT APPLY IN |
| | ASSEMBLY OCCUPANCIES |
| | WHERE OTHERWISE PROVIDED IN CHAPTERS 12 AND 13. |
| | (3)* EXISTING GUARDS ON EXISTING STAIRS SHALL BE |
| | PERMITTED TO BE NOT LESS |
| | THAN 30 IN. (760 MM) HIGH. |
| | |
| | |
| | |
| | 2) THERE IS NO DIMENSION INDICATED BETWEEN THE PICKETS. |
| | |
| | 7.2.2.4.6.3* OPEN GUARDS, OTHER THAN APPROVED EXISTING |
| | OPEN GUARDS, |
| | SHALL HAVE INTERMEDIATE RAILS OR AN ORNAMENTAL PATTERN |
| | SUCH THAT A SPHERE |
| | 4 IN. (100 MM) IN DIAMETER IS NOT ABLE TO PASS THROUGH |
| | ANY OPENING UP |
| | TO A HEIGHT OF 34 IN. |
| | |
| | PLEASE REVIEW AND PROVIDE THE REQUIRED DIMENSION. |
| | |
| | |
| | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |