| 2021-11-01 16:09:14 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2020 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT:21081190 |
| | ADD: 300 S AUSTRALIAN AVE # 507 |
| | CONT: TBD/ TO BE DETERMINED |
| | TEL: |
| | E-MAIL: [email protected] |
| | |
| | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON. NOV. 01/2021 |
| | ACTION: DENIED |
| | |
| | 1) THERE IS NO FLOOR PLAN SHOWING THE AREA WHERE CARPET |
| | IS TO BE REMOVED AND LAMINATE FLOORING INSTALLED. |
| | PLEASE ALSO PROVIDE THE SQUARE FOOTAGE OF THE LAMINATE |
| | FLOORING AND UNDERLAYMENT TO BE INSTALLED. |
| | 2020 W. P. B. ADMINISTRATIVE CODE107.3.5 MINIMUM PLAN |
| | REVIEW CRITERIA |
| | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATIVE CODE SECTION: |
| | 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS AND |
| | OR STRUCTURES. |
| | 107.3.5.1 COMMERCIAL BUILDINGS |
| | 107.3.5.1.1. BUILDING |
| | MISSING: FLOOR PLAN. |
| | |
| | 2) CONTRACTOR CREATED PLANS. CERTIFICATION BY |
| | CONTRACTOR. 107.3.4.3. THE CONTRACTOR (QUALIFIER) THAT |
| | CREATED / DREW THE SET OF PLANS WILL NEED TO IDENTIFY |
| | THEMSELVES AS THE AUTHOR OF THE PLANS. PLEASE PRINT |
| | YOUR NAME, SIGN YOUR NAME AND LICENSE NUMBER FOR THE |
| | TRADE YOU ARE LICENSED IN AND PLANS DRAWN. |
| | |
| | 3) THE PERMIT VALUE CAN NOT BE REVIEWED WITHOUT THE SQ. |
| | FOOTAGE OF THE LAMINATE FLOORING AND UNDERLAYMENT. |
| | 109.3 BUILDING PERMIT VALUATION. IF, IN THE OPINION OF |
| | THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF |
| | BUILDING, OR ALTERATION APPEARS TO BE UNDERESTIMATED ON |
| | THE APPLICATION, THE PERMIT SHALL BE DENIED. FOR |
| | PERMITTING PURPOSES, VALUATION OF BUILDINGS AND OR |
| | ALTERATIONS SHALL BE TOTAL REPLACEMENT PURPOSES, |
| | VALUATION OF THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| | ARCHITECTURAL AND DESIGN FEES, MARKETING COST, OVERHEAD |
| | AND PROFIT; EXCLUDING ONLY LAND VALUE. VALUATION |
| | REFERENCES MAY INCLUDE THE LATEST PUBLISHED DATA OF |
| | NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| | (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS |
| | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| | CONGRESS. |
| | |
| | 4) FLOOR INSULATION/ UNDERLAYMENT (FBC-B 2020) FOR |
| | TILE, STONE, MARBLE, VINYL LAMINATE FLOORING AND WOOD |
| | FLOORING ALL NEED TO HAVE HAD THE SOUND UNDERLAYMENT |
| | TESTED FLOOR ASSEMBLIES TO THE FOLLOWING STANDARDS AND |
| | MEET THE QUALIFICATIONS LISTED UNDER EACH OF THE |
| | STANDARDS FOR A 6 INCH CONCRETE FLOOR ASSEMBLY/ NO |
| | DROPPED CEILING: |
| | PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR |
| | TYPE II BUILDINGS SHOWING COMPLIANCE WITH: |
| | |
| | 4A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492. |
| | |
| | 4B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS, |
| | PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING |
| | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR |
| | AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E |
| | 90. |
| | |
| | 4C) FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2. |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| | |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | |
| | 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | |
| | |
| | AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING |
| | FROM CITY HALL. |
| | MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| | PART-TIME/ RETIRED. |
| | |
| | IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| | BACK INTO THE OFFICE CALL |
| | (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |
| | THANK YOU. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |