2021-09-03 07:58:411ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21081172
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE LIFE SAFETY PLAN SHOWS THE ENTIRE EAST SIDE OF
 THE BUILDING ALONG WITH THE CORRIDOR AND BATH AS BEING
 IN THE SCOPE OF WORK. SHEET M7.1 ONLY SHOWS A SMALL
 PORTION OF UNIT 700. PLEASE PROVED COMPLETE DRAWINGS
 FOR THE TENANT SPACE.
  
 2) PLEASE PROVIDE OUTDOOR AIR CALCULATIONS BASED ON THE
 USE OF EACH SPACE PER FBC M 403.3.1.1 AND TABLE
 403.3.1.1. PROVIDING OUTDOOR AIR CALCULATIONS BY THE
 WSHP?S DOES NOT SHOW ME CALCULATIONS FOR USE OF SPACE
 I.E. OFFICE, CONFERENCE ROOMS, RECEPTION AREA, STORAGE?
  
 3) PLEASE SHOW THE CONDENSATION LINE AND TERMINATION
 LOCATION. FBC M 307
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  