Plan Review Notes
Plan Review Notes For Permit 21081169
Permit Number 21081169
Review Stop M
Sequence Number 1
Notes
Date Text
2021-08-27 09:07:001ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21081169
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M1.2: PLEASE EXPLAIN THE USE OF A FIRE DAMPER
 IN THE NEW 12/12 FRESH AIR TRANSFER DUCT FOR THE FIRE
 PUMP ROOM. ISN?T THE IDEAL TO HAVE OUTDOOR AIR TO THE
 PUMP WHEN IT IS RUNNING?
  
 2) SHEET M1.2: PLEASE EXPLAIN WHY THE NEW 12/12
 TRANSFER DUCT IS ONLY COMING FROM THE STORAGE ROOM
 T1004 AND NOT FROM THE OUTSIDE. THE AIR FOR THE PUMP
 ROOM SHOULD COME FROM THE EXTERIOR OF THE BUILDING.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS