| Plan Review Notes For Permit 21081169 |
| Permit Number |
21081169 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-08-27 09:07:00 | 1ST REVIEW FBC-2020 MECHANICAL | | | PERMIT-21081169 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M1.2: PLEASE EXPLAIN THE USE OF A FIRE DAMPER | | | IN THE NEW 12/12 FRESH AIR TRANSFER DUCT FOR THE FIRE | | | PUMP ROOM. ISN?T THE IDEAL TO HAVE OUTDOOR AIR TO THE | | | PUMP WHEN IT IS RUNNING? | | | | | | 2) SHEET M1.2: PLEASE EXPLAIN WHY THE NEW 12/12 | | | TRANSFER DUCT IS ONLY COMING FROM THE STORAGE ROOM | | | T1004 AND NOT FROM THE OUTSIDE. THE AIR FOR THE PUMP | | | ROOM SHOULD COME FROM THE EXTERIOR OF THE BUILDING. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|