2021-09-01 11:10:5209/01/21 1 ST GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. WOULD YOU PLEASE HAVE A SIGNATURE ON THE ISOMETRIC
 DRAWING OF THE PERSON DESIGNING THE SYSTEM, NOT IN
 ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODE
 61G15-23.001, FLORIDA STATUTE 471 PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.1 GENERAL.
  
 2. WOULD YOU PLEASE SHOW THE CORRESPONDING EHD NUMBER
 OF THE CORRUGATED STAINLESS STEEL TUBING FOR EACH PIPE
 SIZE PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 3. LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM; ADD THE FUTURE, PLEASE. REFER
 TO THE 2020 FBC RES. SEC. G2413.
  
 4. THIS IS A TWO-STORY HOME, AND THE LAYOUT OF THE GAS
 ON THE ISOMETRIC IS NOT UNDERSTANDABLE. WOULD YOU
 PLEASE PROVIDE A MORE COMPREHENSIVE GAS RISER DIAGRAM
 PER THE WPB AMENDMENTS TO THE FBC SEC. 107.3.5.3 (12)
 RESIDENTIAL GAS?
  
 5. WOULD YOU PLEASE PROVIDE MANUFACTURES SPECIFICATIONS
 FOR ALL GAS EQUIPMENT FUTURE AND NEW PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 6. WOULD YOU PLEASE SUBMIT A HOUSE PLAN SHOWING THE
 LOCATION OF THE TANK-LESS WATER HEATER AND THE LOCATION
 AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN
 RELATION TO THE WATER HEATER? THE LOCATION OF THE WATER
 HEATER SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE
 HAND-DRAWN PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1. INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 7. GAS UNITS MAY REQUIRE CONDENSATE, AND THEY NEED TO
 BE 1' AWAY FROM THE STRUCTURE PER THE 2020 FBC SEC
 R318.5. A NOTE ON ISO WILL BE OK.
  
 8. HOT WATER LINES NOT IN CONDITION SPACE NEED TO BE
 INSULATED WITH A MINIMUM R-3 PER THE 2020 FBC SEC. RE
 403.5.3. A NOTE ON ISO WILL BE OK.
  
 9. THIS TANK-LESS UNIT CALL FOR A 10.5 INCHES WATER
 COLUMN, AND THE SERVICE METER DISCHARGES IS A 12 INCH
 WATER COLUMN REQUIRING A REGULATOR FOR THIS UNIT AS PER
 THE MANUFACTURER'S SPECIFICATION. PLEASE SHOW THE
 REGULATOR ON ISO. REGULATORS INSTALLED ON THE EXTERIOR
 OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION PER THE 2020 FBC RES. SEC. G2421.1.
  
 10. WOULD YOU PLEASE SHOW ALL UNIONS IN FRONT OF
 REGULATOR 1 FOOT OF EITHER SIDE PER THE 2020 FBC RES?
 SEC G2421.2.
  
 11. WOULD YOU PLEASE SHOW THE SHUTOFF VALVE ON GAS
 ISOMERIC PER THE 2020 FBC FG SEC. 409.5 OR 2020 FBC
 RES. SEC. G2420.5.
  
 12. THE SHUT-OFF INSIDE SHALL BE ACCESSIBLE WITHOUT
 MOVING THE EQUIPMENT PER THE 2020 FBC SEC. G2403 (202)
 GD, ACCESS. A NOTE ON ISO WILL BE OK.
  
 13. SHOW DRIP LEG ON EQUIPMENT INSTALLED, EXCEPT FOR
 APPLIANCES, RANGE, DRYERS & OD GRILLS PER THE 2020 FBC
 FG 408.2 OR 2020 FBC RES. SEC. G2419.2.
  
 14. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2020
 FBC RES. SEC. G2407.1 AND G2439.4 (CLOTHES DRYERS).
  
 15. IF USING LOVERS FOR COMBUSTION AIR, PLEASE SHOW THE
 LOCATION OF THE LOUVERS THAT ARE BEING INSTALLED. THE
 LOUVERS CANNOT BE LOCATED ON AN EXTERIOR WALL THAT IS
 FIRE RATED AS THE FIRE RATING OF THE WALL MUST BE
 MAINTAINED PER THE WPB AMENDMENTS TO FBC SEC.107.2.1.
  
 16. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION PER THE FBC
 RES. SEC. G2413.2 AND G2404.3.
  
 17. NEED A SHUTOFF VALVE AND HARD CAP FOR FUTURE RANGE
 SHOW ON GAS ISOMERIC SHUTOFF 2020 FBC RES. SEC.
 G2401.1.3.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  