Text |
| 2021-10-10 17:26:15 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. FBC 107, LOCATION OF PROPOSED WALL IS NOT CLEAR. | | | REVISE SITE PLAN TO SHOW LOCATION. | | | | | | 2. THE ENGINEERING SUBMITTED HAS A WIND DESIGN OF 115 | | | MPH. SEE FBC R 301, 150 MPH MINIMUM REQUIRED. | | | | | | 3. FBC 107, ENGINEERING STATES THAT THIS IS NOT A | | | RETAINING WALL. PROVIDE A PLAN THAT SHOWS GRADE | | | ELEVATIONS ON BOTH SIDES OF THE PROPOSED WALL. | | | | | | 4. FBC R 322 THE WALL MUST RESIST FLOOD LOADS TO 8' AND | | | 9' NAVD88. REVISE PLAN TO INCLUDE FLOOD DESIGN | | | CRITERIA. | | | | | | |
|