Notes
Date Text
2021-10-10 17:26:15****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC 107, LOCATION OF PROPOSED WALL IS NOT CLEAR.
 REVISE SITE PLAN TO SHOW LOCATION.
  
 2. THE ENGINEERING SUBMITTED HAS A WIND DESIGN OF 115
 MPH. SEE FBC R 301, 150 MPH MINIMUM REQUIRED.
  
 3. FBC 107, ENGINEERING STATES THAT THIS IS NOT A
 RETAINING WALL. PROVIDE A PLAN THAT SHOWS GRADE
 ELEVATIONS ON BOTH SIDES OF THE PROPOSED WALL.
  
 4. FBC R 322 THE WALL MUST RESIST FLOOD LOADS TO 8' AND
 9' NAVD88. REVISE PLAN TO INCLUDE FLOOD DESIGN
 CRITERIA.
  
  