2021-10-05 15:12:001) PLEASE PROVIDE THE REQUIRED INFORMATION FOR
 ALLOWABLE REFRIGERANT QUANTITY BASED ON TYPE OF
 REFRIGERANT SYSTEM CLASSIFICATION AND OCCUPANCY FOR
 EACH SYSTEM. FBC M 1102.1- 3
  
 2) PLEASE ADD THE FOLLOWING NOTE TO THE DRAWINGS: FBC M
 1108.4 DECLARATION. A CERTIFICATE OF TEST SHALL BE
 PROVIDED FOR ALL SYSTEMS CONTAINING 55 POUNDS (25 KG)
 OR MORE OF REFRIGERANT. THE CERTIFICATE SHALL GIVE THE
 NAME OF THE REFRIGERANT AND
 THE FIELD TEST PRESSURE APPLIED TO THE HIGH SIDE AND
 THE LOW SIDE OF THE SYSTEM. THE CERTIFICATION OF TEST
 SHALL BE SIGNED BY THE INSTALLER AND SHALL BE MADE PART
 OF THE PUBLIC RECORD.
  