| Plan Review Notes For Permit 21081141 |
| Permit Number |
21081141 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-09-20 14:23:56 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) PROVIDE AN ELEVATION VIEW OF THE WINDOWS. SHOW THE | | | CONFIGURATION AND DIMENSIONS OF THE WINDOWS AND THE | | | LOCATIONS AND SPANS OF THE MULLIONS. FBC 107.2.1 | | | | | | 2) ON PRODUCT APPROVAL FL15816.14 THE DESIGN PRESSURE | | | OF +/- 50 PSF IS CIRCLED. THE WINDLOAD SHEET HAS THE DP | | | AS 65 FOR THIS FL#. PLEASE CLARIFY. FBC 107.2.1 | | | | | | 3) THE PRODUCT HAS TO MEET BOTH THE POSITIVE AND | | | NEGATIVE DESIGN PRESSURES. PLEASE SPECIFY BOTH OF THE | | | PRESSURES YOUR WIND LOAD SHEET FOR THIS PROJECT. FBC | | | 107.2.1 |
|