Plan Review Notes
Plan Review Notes For Permit 21081124
Permit Number 21081124
Review Stop M
Sequence Number 2
Notes
Date Text
2021-09-07 08:00:062ND REVIEW FBC-2020 MECHANICAL
 PERMIT-21081124
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE THE CALCULATIONS AND INFORMATION FOR
 THE REFRIGERATION SYSTEMS PER FBC M 1102 BELOW:
  
 SECTION 1102
 SYSTEM REQUIREMENTS
 1102.1 GENERAL. THE SYSTEM CLASSIFICATION, ALLOWABLE
 REFRIGERANTS, MAXIMUM QUANTITY, ENCLOSURE REQUIREMENTS,
 LOCATION LIMITATIONS, AND FIELD PRESSURE TEST
 REQUIREMENTS SHALL BE DETERMINED AS FOLLOWS:
 1. DETERMINE THE REFRIGERATION SYSTEM'S CLASSIFICATION,
 IN ACCORDANCE WITH SECTION 1103.3.
  
 2. DETERMINE THE REFRIGERANT CLASSIFICATION IN
 ACCORDANCE WITH SECTION 1103.1.
  
 3. DETERMINE THE MAXIMUM ALLOWABLE QUANTITY OF
 REFRIGERANT IN ACCORDANCE WITH SECTION 1104, BASED ON
 TYPE OF REFRIGERANT, SYSTEM CLASSIFICATION AND
 OCCUPANCY.
  
 4. DETERMINE THE SYSTEM ENCLOSURE REQUIREMENTS IN
 ACCORDANCE WITH SECTION 1104.
  
 5. REFRIGERATION EQUIPMENT AND APPLIANCE LOCATION AND
 INSTALLATION SHALL BE SUBJECT TO THE LIMITATIONS OF
 CHAPTER 3.
  
 6. NON-FACTORY-TESTED, FIELD-ERECTED EQUIPMENT AND
 APPLIANCES SHALL BE PRESSURE TESTED IN ACCORDANCE WITH
 SECTION 1108.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  