Plan Review Notes
Plan Review Notes For Permit 21081121
Permit Number 21081121
Review Stop FIRE
Sequence Number 4
Notes
Date Text
2022-03-17 12:06:45THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) NOW THAT THE SPECIFIC LOCATION HAS BEEN PROVIDED IT
 APPEAR TO BE IN CLOSE PROXIMITY TO THE GENERATOR AIR
 INTAKE WHICH MAY INDUCE HEATED AND TOXIC EXHAUST GAS
 BACK INTO THE GENERATOR.
  
 THE CONTINUED RUN LENGTH OF THE GENERATOR WITH CONSTANT
 HEATED EXHAUST MAY RENDER HIGHT TEMPAURATIRE AND
 RESULTANT FAILURE OF THE SYSTEM.
  
 PER NFPA 37
  
 8.2.3 EXHAUST SYSTEM TERMINATION.
 8.2.3.1* EXHAUST SYSTEMS SHALL TERMINATE OUTSIDE THE
 STRUCTURE
 AT A POINT WHERE HOT GASES, SPARKS, OR PRODUCTS OF
 COMBUSTION
 WILL DISCHARGE TO A SAFE LOCATION.
  
 A.8.2.3.1 EXHAUST SYSTEMS SHOULD NOT TERMINATE UNDER
 STRUCTURES
 (INCLUDING LOADING PLATFORMS) OR WHERE EXHAUST GAS
 ENTRAINMENT
 INTO VENTILATION INTAKES MIGHT OCCUR.
  
 7.7 HEATING, COOLING, AND VENTILATING.
 7.7.1* WITH THE EPS RUNNING AT RATED LOAD, VENTILATION
 AIRFLOW
 SHALL BE PROVIDED TO LIMIT THE MAXIMUM AIR TEMPERATURE
 IN THE
 EPS ROOM OR THE ENCLOSURE HOUSING THE UNIT TO THE
 MAXIMUM
 AMBIENT AIR TEMPERATURE REQUIRED BY THE EPS
 MANUFACTURER.
  
 PER NFPA 110
  
 7.10 EXHAUST SYSTEM.
 7.10.1 THE EXHAUST SYSTEM EQUIPMENT AND INSTALLATION,
 INCLUDING
 PIPING, MUFFLER, AND RELATED ACCESSORIES, SHALL BE IN
 ACCORDANCE WITH NFPA37, STANDARD FOR THE INSTALLATION
 AND USE OF
 STATIONARY COMBUSTION ENGINES AND GAS TURBINES, AND
 OTHER APPLICABLE
 STANDARDS.
 7.10.2 EXHAUST SYSTEM INSTALLATION SHALL BE GASTIGHT TO
 PREVENT
 EXHAUST GAS FUMES FROM ENTERING INHABITED ROOMS OR
 BUILDINGS
 AND TERMINATE IN SUCH A MANNER THAT TOXIC FUMES CANNOT
 REENTER A BUILDING OR STRUCTURE, PARTICULARLY THROUGH
 WINDOWS,
 AIR VENTILATION INLETS, OR THE ENGINE AIR-INTAKE
 SYSTEM.
  
  
 IT APPEARS THAT THE EXHAUST IS LOCATED WITHIN 5' TO 10'
 OF THE GENERATOR AIR INTAKE AND THE OPENING INTO THE
 PARKING GARAGE ON THE SAME WALL.
  
 THIS LOCATION APPEARS TO CONFLICT WITH THE CODE AND
 INTENT FOR A REMOTE EXHAUST LOCATION.
  
 THE PROVIDED MANUFACTURE'S SPECIFICATION SHEETS DO NOT
 INDICATE A RECOMMENDED DISTANCE.
  
 PLEASE REVIEW AND PROVIDE A DETAILED REVIEW OF THE
 DISTANCE FROM THE EHAUST TO BOTH THE GENERATOR AIR
 INTAKE AND THE OPENEING TO THE GARAGE
 CONTAINED IN THE MANUFACTURE'S INSTALLATION
 SPECIFICATION RECOMMENDATIONS AND/OR REQUIREMENTS.
  
 PLEASE INDICATE HOW THIS INSTALLATION MEETS THOSE
 REQUIRMENTS AND THE NFPA CODES.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  