| Plan Review Notes For Permit 21081121 |
| Permit Number |
21081121 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-09-03 13:24:39 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) THERE ARE NO INDICATIONS OF THE LOCATION OF THE | | | GENERATOR WITHIN THE SITE/BUILDING COMFIMR PREVIOS | | | REVIEWS. | | | | | | FOR THE OFFICIAL RECORD PLEASE REVIEW AND PROVIDE THE | | | LOCATION. | | | | | | | | | 1A) THERE ARE NO INDICATIONS OF THE LOCATION OF THE | | | GENERATOR EXHAUST SHOWING COMPLIANCE WITH NFPA 110 & 37 | | | | | | PLEASE REVIEW AND PROVIDE THE LOCATION, SIZE, AND | | | INSTALLATION DETAILS IN COMPLIANCE OF THE CODE. | | | | | | | | | | | | 1B) THERE ARE INDICATIONS OF NG FUEL SOURCE; HOWEVER, | | | NO DETAILS OF FUEL LINE TYPE, LENGTH, LOCATION, ETC., | | | IN COMPLIANCE WITH NFPA 54 AND OTHER APPLICABLE NFPA | | | CODES. | | | | | | | | | PLEASE REVIEW AND PROVIDE DETAILS. | | | | | | | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|