| 2022-04-04 11:27:02 | PLAN REVIEW COMMENTS |
| | |
| | 6 TH REVIEW: FBC SEVENTH EDITION (2020) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | |
| | NOTE: IT IS ACKNOWLEDGED BY THE CITY BUILDING DIVISION |
| | THAT THESE ROLL-UP STORM SHUTTERS PROPOSED FOR THE ROOF |
| | TOP GAZEBO ARE NOT REQUIRED TO BE INSTALLED BY THE |
| | FLORIDA BUILDING CODE. |
| | |
| | 1) PROVIDE A LETTER FROM A FLORIDA LICENSED ENGINEER |
| | AFFIRMING THAT THE INSTALLATION OF THESE ROLL-UP STORM |
| | SHUTTERS WILL NOT HAVE AN ADVERSE EFFECT ON THE HOST |
| | STRUCTURE WHEN IN USE DURING A WIND EVENT. FBC 1604.2 & |
| | 107.2.1 |
| | |
| | 2) PLEASE HAVE THE ENGINEER EXPLAIN THE SUBSTANTIAL |
| | PRESSURE DIFFERENCE BETWEEN THE DESIGN PRESSURES FOR |
| | OPENING #1 AND THE OTHER OPENINGS. ESPECIALLY OPENING |
| | #5 WHICH IS IN THE SAME WALL ZONE AND IS 134.5 SQFT |
| | COMPARED TO 202.5 SQFT. FBC 1604.2 |
| | |
| | 3) SUBMIT A CORRECTED HURRICANE SHUTTER INSTALLATION |
| | SCHEDULE. FBC 107.2.1 |
| | |
| | 4) ON SHEET 9 OF 29 OF THE MULLION PRODUCT APPROVAL |
| | (FL13068-R5), THE DESIGN PRESSURE OF 105 PSF IS CIRCLED |
| | FOR THE AVERAGE SPAN WIDTH OF UP TO 132" AND A MULLION |
| | LENGTH UP TO 144". I BELIEVE THAT THE OPENING IN |
| | QUESTION IS 197" WIDE AND 148" IN HEIGHT (BASED ON |
| | INFORMATION THAT WAS PREVIOUSLY PROVIDED). THE REQUIRED |
| | LENGTH FOR THE MULLION WOULD EXCEED THE 144" MULLION |
| | LENGTH ALLOWED BY THE PRODUCT APPROVAL. PLEASE CLARIFY. |
| | FBC 107.2.1 & 1604.2 |
| | |
| | 5) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH |
| | OF THE REVIEW COMMENTS HAS BEEN ADDRESSED. |
| | |
| | |
| | |