| 2021-09-21 16:39:29 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC SEVENTH EDITION (2020) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) THE LOCATION OF THE PROJECT IS TOO VAGUE. SUBMIT |
| | ADDITIONAL INFORMATION TO SPECIFY THE EXACT LOCATION OF |
| | WHERE THE SHUTTERS WILL BE INSTALLED. PROVIDE |
| | ELEVATIONS OF THE BUILDING AND A BUILDING FLOOR PLAN |
| | FOR THE LEVEL WHERE THE UNIT IS LOCATED WITH THE |
| | SPECIFIC UNIT IDENTIFIED. FBC AMENDMENTS 107.2.1 |
| | |
| | 2) THIS IS A HIGH RISE BUILDING THAT IS MORE THAN 60 |
| | FEET IN HEIGHT. SUBMIT SIGNED AND SEALED DESIGN |
| | PRESSURES FROM A FLORIDA LICENSED ENGINEER. SUBMIT |
| | REQUIRED COMPONENT AND CLADDING DESIGN PRESSURES FOR |
| | THE OPENINGS THAT HAVE BEEN PREPARED BY A FLORIDA |
| | LICENSED ENGINEER. THE DOCUMENTS ARE REQUIRED TO BE |
| | DIGITALLY SIGNED BY THE ENGINEER IF SUBMITTED |
| | ELECTRONICALLY AND THE ENGINEER'S ORIGINAL HANDWRITTEN |
| | SIGNATURE IF PAPER DOCUMENTS ARE SUBMITTED. FS 471 & |
| | FAC 61G15 AND FBC AMEND. 107.1 |
| | |
| | 3) A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE |
| | COMPLETED AT THIS TIME DUE TO LACK OF INFORMATION ON |
| | THE SUBMITTED PLANS. ADDITIONAL PLAN REVIEW COMMENTS |
| | MAY BE GENERATED WHEN MORE INFORMATION IS PROVIDED. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |