| Plan Review Notes For Permit 21081037 |
| Permit Number |
21081037 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-09-28 14:40:11 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) 70 AMPERE TAP ON LOAD SIDE OF MAIN SHALL COMPLY WITH | | | 705.12 | | | | | | 705.12 (B) LOAD SIDE. THE OUTPUT OF AN INTERCONNECTED | | | ELECTRIC POWER SOURCE SHALL BE PERMITTED TO BE | | | CONNECTED TO THE LOAD | | | SIDE OF THE SERVICE DISCONNECTING MEANS OF THE OTHER | | | SOURCE(S) AT ANY DISTRIBUTION EQUIPMENT ON THE | | | PREMISES. WHERE DISTRIBUTION | | | EQUIPMENT, INCLUDING SWITCHGEAR, SWITCHBOARDS, OR | | | PANELBOARDS, IS FED SIMULTANEOUSLY BY A PRIMARY | | | SOURCE(S) OF | | | ELECTRICITY AND ONE OR MORE OTHER POWER SOURCE(S), AND | | | WHERE THIS DISTRIBUTION EQUIPMENT IS CAPABLE OF | | | SUPPLYING MULTIPLE | | | BRANCH CIRCUITS OR FEEDERS, OR BOTH, THE | | | INTERCONNECTING PROVISIONS FOR OTHER POWER SOURCES | | | SHALL COMPLY WITH 705.12(B)(1) | | | THROUGH (B)(5). | | | | | | 2) BOX BELOW 200A PANEL ON RISER? WHAT IS IT FOR? | | | | | | 3) POLARIS TAPS IN METERMAIN COMBO? TAPPING WHAT? | | | | | | 4) IS VALUE $5K OR $55K ? |
|