| 2021-09-14 11:31:01 | 1ST REVIEW FBC-2020 PLUMBING | | | PERMIT- 21081019 | | | 9/14/21 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | | 2020 | | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET P3.1: SHOW THE LOCATIONS OF THE REQUIRED FULL | | | OPEN SHUTOFF VALVE AND CHECK VALVE ON THE DISCHARGE | | | PIPING. PLEASE NOTE THE VALVES SHALL BE IN LOCATIONS | | | THAT ALLOWS ACCESS- SECTION 712.2 FBC P. | | | | | | 2) P3.1: SHOW THE LOCATIONS OF WATER HAMMER ARRESTORS | | | AND BACKFLOW PREVENTERS ON SUPPLY LINES TO THE COFFEE | | | MAKER AND REFRIGERATOR ICE MAKER- SECTIONS 604.9 & | | | 608.3 FBC P. | | | | | | 3) A1, A3.1: PLEASE SHOW A CLEAR FLOOR SPACE PARALLEL | | | APPROACH DIAGRAM AT THE SINK IN THE BREAK ROOM- SECTION | | | 606.2 FBC ACC. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|