2021-09-14 11:31:011ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21081019
 9/14/21
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P3.1: SHOW THE LOCATIONS OF THE REQUIRED FULL
 OPEN SHUTOFF VALVE AND CHECK VALVE ON THE DISCHARGE
 PIPING. PLEASE NOTE THE VALVES SHALL BE IN LOCATIONS
 THAT ALLOWS ACCESS- SECTION 712.2 FBC P.
  
 2) P3.1: SHOW THE LOCATIONS OF WATER HAMMER ARRESTORS
 AND BACKFLOW PREVENTERS ON SUPPLY LINES TO THE COFFEE
 MAKER AND REFRIGERATOR ICE MAKER- SECTIONS 604.9 &
 608.3 FBC P.
  
 3) A1, A3.1: PLEASE SHOW A CLEAR FLOOR SPACE PARALLEL
 APPROACH DIAGRAM AT THE SINK IN THE BREAK ROOM- SECTION
 606.2 FBC ACC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  