Plan Review Notes
Plan Review Notes For Permit 21080967
Permit Number 21080967
Review Stop P
Sequence Number 1
Notes
Date Text
2021-08-25 11:00:5708/25/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON SHEET S-1 WOULD YOU PLEASE PROVIDE SLAB REPAIR
 DETAIL FOR REVIEW. SHOW THE WIDTH OF THE REPAIR, THE
 MINIMUM THICKNESS OF THE CONCRETE TO BE REPLACED, AND
 THE PSI OF THE CONCRETE. SHOW THE SIZE AND LENGTH OF
 THE DOWELS, THE MINIMUM EMBEDMENT DEPTH INTO THE
 EXISTING SLAB, AND THE SPACING OF THE DOWELS IN THE
 CENTER. THE REPAIR SHALL ALSO INCLUDE TERMITE TREATMENT
 OF THE SOIL AND THE REQUIRED VAPOR BARRIER OVER THE
 SOIL. A COPY OF THE TERMITE CERTIFICATE SHALL BE ONSITE
 FOR A FINAL INSPECTION.
  
 2. ON SHEET P-1;
 A. THE WASHING MACHINE SHUT OFF VALVES SHALL BE
 ACCESSIBLE WITHOUT MOVING OF THE UNITS AND WITHIN REACH
 PER THE 2020 FBC SEC. R 2903.9.3.
  
 B. HOT WATER LINES UNDERGROUND NOT IN CONDITION SPACE
 NEED TO BE INSULATED WITH A MINIMUM R-3 PER THE 2020
 FBC SEC. RE 403.5.3.
  
 C. THE WASHING MACHINE SHUT OFF VALVES SHALL BE
 ACCESSIBLE WITHOUT MOVING OF THE UNITS AND WITHIN REACH
 PER THE 2020 FBC SEC. R 2903.9.3.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR