Plan Review Notes
Plan Review Notes For Permit 21080941
Permit Number 21080941
Review Stop B
Sequence Number 1
Notes
Date Text
2021-09-24 17:13:50****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. PAGE 7 OF THE ENGINEERING CITES THE DESIGN CRITERIA
 OF FBC B 3105 WHICH REQUIRES THAT THE AWNING BE
 RETRACTED WHEN WINDS OVER 35MPH ARE ANTICIPATED, FABRIC
 TO BE REMOVED IN THE EVENT OF WINDS IN EXCESS OF 75
 MPH. HOW WILL THIS BE ACCOMPLISHED?
  
 FBC 107, PROVIDE THE FOLLOWING INFORMATION:
  
 PROVIDE INSTRUCTIONS ON FABRIC REMOVAL, INCLUDING TOOLS
 NECESSARY.
  
 WHO WILL BE RESPONSIBLE FOR REMOVING THE FABRIC?
  
 WILL THIS BE INCORPORATED INTO THE HOTEL O&M OR OTHER
 DOCUMENTS, HURRICANE PLAN?
  
  
  
  
  
  