| Date |
Text |
| 2021-08-26 13:07:30 | 08/26/21 1ST GAS REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. WOULD YOU PLEASE HAVE A SIGNATURE ON THE ISOMETRIC |
| | DRAWING OF THE PERSON DESIGNING THE SYSTEM, NOT IN |
| | ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODE |
| | 61G15-23.001, FLORIDA STATUTE 471 PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.1 GENERAL. |
| | |
| | 2. WOULD YOU PLEASE SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS THE LENGTH OF ALL CUT SECTIONS OF PIPE |
| | PER 2020 FBC RES. SECS. G2413.4.1, G2413.4.2. |
| | |
| | 3. WOULD YOU PLEASE SHOW THE DISTANCE FROM THE POINT OF |
| | THE DELIVERY GAS METER TO THE MOST REMOTE OUTLET IN THE |
| | BUILDING AND/OR SYSTEM PER THE 2020 FBC RES. SEC. |
| | G2413.4.1. |
| | |
| | 4. WOULD YOU PLEASE PROVIDE THE SIZING TABLE OR NOTE |
| | THE PLANS PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 5. WOULD YOU PLEASE SUBMIT THE MANUFACTURER'S |
| | SPECIFICATION SHEETS/INSTALLATION MANUAL FOR TANK-LESS |
| | HEATER EQUIPMENT TO VERIFY COMPLIANCE WITH 2020 FBC |
| | RES. SEC.G2408.1. |
| | |
| | 6. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE |
| | INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT |
| | SHALL BE ONSITE AT THE TIME OF INSPECTION PER THE 2020 |
| | FBC FG SECS. 402.2 AND 301.3. |
| | |
| | 7. WOULD YOU PLEASE SHOW AND LABEL ALL UNIONS IN FRONT |
| | OF REGULATOR 1FOOT OF EITHER SIDE PER THE 2020 FBC RES. |
| | SEC G2421.2? |
| | |
| | 8. WOULD YOU PLEASE SHOW AND LABEL THE SHUT-OFF, AND |
| | THEY SHALL BE ACCESSIBLE WITHOUT MOVING THE EQUIPMENT |
| | PER THE 2020 FBC SEC. G2403 (202) GD, ACCESS. |
| | |
| | 9. WOULD YOU PLEASE SHOW AND LABEL ALL DRIP LEGS ON |
| | EQUIPMENT EXCEPT FOR APPLIANCES, RANGE, DRYERS & OD |
| | GRILLS PER THE 2020 FBC RES. SEC. G2419.2. |
| | |
| | 10. THIS TANK-LESS UNIT CALL FOR A 10.5 INCHES WATER |
| | COLUMN, AND THE SERVICE METER DISCHARGES IS 2 PSI WHICH |
| | REQUIRES A REGULATOR FOR THIS UNIT AS PER THE |
| | MANUFACTURER'S SPECIFICATION. SUBMIT MANUFACTURER'S |
| | SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS |
| | INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE |
| | APPROVED FOR OUTDOOR INSTALLATION PER THE 2020 FBC RES. |
| | SEC. G2421.1 OR 410.1. |
| | |
| | 11. ALL THE BTU LOADS OF EACH APPLIANCE ARE SHOWN. |
| | WOULD YOU PLEASE SEPARATE EXISTING BTU LOADS FORM NEW |
| | ON THE SYSTEM AND DISPLAY IT ON PLANS PER THE 2020 FBC |
| | RES. SEC. G2413. |
| | |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |