Plan Review Notes
Plan Review Notes For Permit 21080908
Permit Number 21080908
Review Stop NFIP
Sequence Number 2
Notes
Date Text
2022-01-07 14:22:53FLOOD ZONE = AE6
 PROPOSED LOWEST FLOOR ELEVATION = (9.60 NGVD) - 1.52
 PER SURVEY = 8.08 NAVD
  
 CORRECTIONS NEEDED =
  
 1) THERE ARE ROOMS THAT ARE BELOW THE REQUIRED LOWEST
 FLOOR ELEVATION - SUCH AS RESTROOM 01-307 (NOT
 NUMBERED), IT POE 01-305, AND IT POE 01-308 (NOT SURE
 WHAT "IT POE" MEANS) - ONLY VEHICLE PARKING BUILDING
 ACCESS AND STORAGE CAN BE LOWER THAN THE LOWEST FLOOR
 ELEVATION - FBC SECTION 202 LOWEST FLOOR. THE LOWEST
 FLOOR OF THE LOWEST ENCLOSED AREA, INCLUDING BASEMENT,
 BUT EXCLUDING ANY UNFINISHED OR FLOOD-RESISTANT
 ENCLOSURE, USABLE SOLELY FOR VEHICLE PARKING, BUILDING
 ACCESS OR LIMITED STORAGE PROVIDED THAT SUCH ENCLOSURE
 IS NOT BUILT SO AS TO RENDER THE STRUCTURE IN VIOLATION
 OF SECTION 1612.
  
 ORDINANCE NO. 4729-17 SEC. 18-34 - TECHNICAL AMENDMENTS
 TO FLORIDA BUILDING CODE, BUILDING.(B) 1612.4.2
 ELEVATION REQUIREMENTS. THE MINIMUM ELEVATION
 REQUIREMENTS SHALL BE AS SPECIFIED IN ASCE 24 OR THE
 BASE FLOOD ELEVATION PLUS TWO FEET (610MM). WHICHEVER
 IS HIGHER.
  
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  