| 2021-12-17 16:52:20 | 12/14/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. ON SHEET P-200F; |
| | |
| | A. A 4" PIPE 32 DFU SHOWED IN A PRESSURIZATION WELL |
| | STAIR WITH A FIRE-RATED SYSTEM NEET TO HAVE A SHAFT AND |
| | STAIRWELL NOT LABELED. WOULD YOU PLEASE CLARIFY PER THE |
| | WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | B. GREASE INTERCEPTOR SIZE NEEDS TO MAX 750 GALLONS TO |
| | HAVE THE AMOUNT IN SERIES AND IT IS CALLED 1000 |
| | GALLONS. UPON REQUEST, THERE IS A CITY DETAIL TO COMPLY |
| | WITH THESE INTERCEPTORS. |
| | |
| | C. GREASE INTERCEPTORS REQUIRE A SEPARATE PERMIT AND |
| | REVIEW BEFORE INSTALLATION PER THE WPB AMENDMENTS TO |
| | THE FBC SEC. 105.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | 2. ON SHEET P300-F, IT SHOWS HUB DRAINS TRAPS WITH NO |
| | TRAP PRIMES AND NO VENT. WOULD YOU PLEASE CORRECT PER |
| | THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION |
| | ON CONSTRUCTION DOCUMENTS. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | WEST PALM BEACH AMENDMENTS 2017 FBC CHAPTER; UPON |
| | REQUEST. |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |