2021-12-17 16:52:2012/14/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON SHEET P-200F;
  
 A. A 4" PIPE 32 DFU SHOWED IN A PRESSURIZATION WELL
 STAIR WITH A FIRE-RATED SYSTEM NEET TO HAVE A SHAFT AND
 STAIRWELL NOT LABELED. WOULD YOU PLEASE CLARIFY PER THE
 WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 B. GREASE INTERCEPTOR SIZE NEEDS TO MAX 750 GALLONS TO
 HAVE THE AMOUNT IN SERIES AND IT IS CALLED 1000
 GALLONS. UPON REQUEST, THERE IS A CITY DETAIL TO COMPLY
 WITH THESE INTERCEPTORS.
  
 C. GREASE INTERCEPTORS REQUIRE A SEPARATE PERMIT AND
 REVIEW BEFORE INSTALLATION PER THE WPB AMENDMENTS TO
 THE FBC SEC. 105.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 2. ON SHEET P300-F, IT SHOWS HUB DRAINS TRAPS WITH NO
 TRAP PRIMES AND NO VENT. WOULD YOU PLEASE CORRECT PER
 THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 WEST PALM BEACH AMENDMENTS 2017 FBC CHAPTER; UPON
 REQUEST.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  