| Plan Review Notes For Permit 21080907 |
| Permit Number |
21080907 |
|
| Review Stop |
PRIVATEPRV |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2022-05-28 13:34:37 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FS553.791, AN ACCURATE AFFIDAVIT IS REQUIRED PRIOR TO | | | BUILDING DIVISION AUDIT. | | | | | | 1. ELECTRICAL AFFIDAVIT LACKS THE NAME OF THE DESIGN | | | PROFESSIONAL. | | | 2. E-339.A DATE ON THE PLAN DOESN'T MATCH THE | | | AFFIDAVIT. PLAN UPLOADED IS 75%. ALL DOCUMENTS SHOULD | | | BE 100% CONSTRUCTION DRAWINGS. | | | 3. MECHANICAL PAGES APPEAR OK BUT AFFIDAVIT LACKS THE | | | NAME OF THE DESIGN PROFESSIONAL, VERIFY ALL. | | | 4. M703 WAS UPLOADED TO PROJECTDOX, BUT LOCKED AT | | | APPLICANT'S REQUEST. PLEASE REQUEST THAT ALL LOCKED | | | FILES BE DELETED. IT APPEARS THAT THESE ARE SOME FILES | | | THAT SHOULD BE DELETED: | | | A405, A406, A420 | | | 248 WIND DIAGRAMS (DUPLICATE, NOT LOCKED) | | | 5. S-012 WAS UPLOADED TWICE, ONCE INCORRECTLY NAMED, | | | REQUEST THAT IT BE DELETED. | | | 6. A-821, A-415, A-421 ARE NOT ON THE AFFIDAVIT, UNABLE | | | TO LOCATE IN PROJECTDOX. | | | 7. UNABLE TO LOCATE AN AFFIDAVIT FOR FIRE ALARM, | | | TELECOM, SECURITY DRAWINGS. | | | 8. CHECK ALL, THIS LIST MAY NOT BE A COMPLETE LIST OF | | | ALL ERRORS/DISCREPANCIES. | | | | | | |
|