Plan Review Notes
Plan Review Notes For Permit 21080907
Permit Number 21080907
Review Stop PRIVATEPRV
Sequence Number 3
Notes
Date Text
2022-05-28 13:34:37****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FS553.791, AN ACCURATE AFFIDAVIT IS REQUIRED PRIOR TO
 BUILDING DIVISION AUDIT.
  
 1. ELECTRICAL AFFIDAVIT LACKS THE NAME OF THE DESIGN
 PROFESSIONAL.
 2. E-339.A DATE ON THE PLAN DOESN'T MATCH THE
 AFFIDAVIT. PLAN UPLOADED IS 75%. ALL DOCUMENTS SHOULD
 BE 100% CONSTRUCTION DRAWINGS.
 3. MECHANICAL PAGES APPEAR OK BUT AFFIDAVIT LACKS THE
 NAME OF THE DESIGN PROFESSIONAL, VERIFY ALL.
 4. M703 WAS UPLOADED TO PROJECTDOX, BUT LOCKED AT
 APPLICANT'S REQUEST. PLEASE REQUEST THAT ALL LOCKED
 FILES BE DELETED. IT APPEARS THAT THESE ARE SOME FILES
 THAT SHOULD BE DELETED:
 A405, A406, A420
 248 WIND DIAGRAMS (DUPLICATE, NOT LOCKED)
 5. S-012 WAS UPLOADED TWICE, ONCE INCORRECTLY NAMED,
 REQUEST THAT IT BE DELETED.
 6. A-821, A-415, A-421 ARE NOT ON THE AFFIDAVIT, UNABLE
 TO LOCATE IN PROJECTDOX.
 7. UNABLE TO LOCATE AN AFFIDAVIT FOR FIRE ALARM,
 TELECOM, SECURITY DRAWINGS.
 8. CHECK ALL, THIS LIST MAY NOT BE A COMPLETE LIST OF
 ALL ERRORS/DISCREPANCIES.
  
  