Plan Review Notes
Plan Review Notes For Permit 21080907
Permit Number 21080907
Review Stop P
Sequence Number 2
Notes
Date Text
2022-08-24 15:04:242ND REVIEW FBC-2020 PLUMBING
 PERMIT- 21080907
 8/23/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLUMBING PLAN AUDIT.
 FAILED COMMENTS FROM THE 1ST AUDIT ARE PRINTED BELOW
 WITH ADDITIONALS NOTES IN CAP LETTERS FOR
 CLARIFICATION. PLEASE REVIEW THE COIMMENTS BELOW AND
 NOTE THE FOLLOWING:
  
 DUE TO A RECENT CHANGE IN PROCESS, THE POTABLE WATER
 BACKFLOW PREVENTER , GREASE INTERCEPTOR, AND OIL/SAND
 INTERCEPTOR PERMITS ARE REQUIRED TO BE SUBMITTED PRIOR
 TO ISSUANCE OF THE PRIMARY PERMIT. YOU CAN SUBMIT AN
 APPLICATION "TBD" (TO BE DETERMINED) IF YOU DO NOT HAVE
 A CONTRACTOR SELECTED BY EMAILING A COMPLETED PERMIT
 APPLICATION TO [email protected] . YOU WILL
 RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU
 MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE
 APPLICATION IS REQUIRED AT THIS TIME. WE RECOMMEND THAT
 YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME. AFTER
 YOU HAVE THE PERMIT(S) GENERATED, NOTIFY ME VIA EMAIL
 AND I WILL CHANGE THE REVIEW STATUS TO PASS.
  
 2) FAILED ITEM 2B SHEET LS-101: BOH: B OCCUPANCY- 2
 WATER CLOSETS AND 2 LAVATORIES ARE REQUIRED- 1 EACH FOR
 MALE AND FEMALE USE. PLEASE NOTE SEPARATE FACILITIES
 FOR MALE AND FEMALE USE ARE REQUIRED- SEE SEC. 403.2.
 ITEM #4 AND CORRECT THE CALCULATIONS. REVISED SHEET
 LS-100: THE CALCULATIONS ARE NOT BROKEN DOWN PER GENDER
 AND INDICATE A DEFICIENCY OF 1 WATER CLOSET AND 1
 LAVATORY.
  
 12) FAILED. P-200: COMMENT #11 IS ALSO APPLICABLE TO
 THE OIL INTERCEPTOR. PROVIDE INSTALLATION DETAILS AND
 NOTES ON THE PLAN, AND SUBMIT MANUFACTURERS
 INSTALLATION GUIDELINES FOR HIGH WATER AND HYDROSTATIC
 PRESSURE CONDITIONS, AND FOR VEHICULAR LOAD PROTECTION.
 THE NARRATIVE RESPONSE INDICATES FLOWABLE FILL DETAILS
 ON P-504, HOWEVER THE DETAILS THERE ARE FOR THE SCHIER
 INTERCEPTOR. DETAILS FOR THE ZURN OIL INTERCEPTOR WHICH
 IS SHOWN ON P-505 ARE NOT PROVIDED.
  
 13) FAILED. P-200: PROVIDE RAIN WATER CISTERN
 INSTALLATION DETAILS AND NOTES ON THE PLAN AND SUBMIT
 MANUFACTURERS SPECIFICATIONS FOR THE TANK AND THE
 MANHOLE COVER. THE TANK AND COVER SHALL BE WATER TIGHT
 AND DESIGNED TO WITHSTAND HIGH WATER AND HYDROSTATIC
 PRESSURE CONDITIONS- SEC.- 309.2 FBC P AND SEC. 7.3.2
 ASCE 24-14. BASED ON THE RESPONSE NARRATIVE PLEASE
 IDENTIFY THE WATER TANK SHOWN ON THE PLAN AS A CONCRETE
 RAIN CISTERN. PLEASE SHOW THE LOCATION OF THE MANHOLE
 ON THE PLAN AND PROVIDE EITHER NOTES OR DETAILS
 VERIFYING THE COVER WILL BE MINIMUM 24-INCHES IN
 DIAMTER, WATER TIGHT, AND LOCKABLE- SECS. 1301.9.6 AND
 1303.12 FBC P. PLEASE NOTE THAT NON-POTABLE SIGNAGE IS
 REQUIRED PER SEC.- 1301.3.
  
 15) FAILED. P-200: A WASTE RECEPTOR IS NOT SHOWN IN THE
 TRASH COMPACTOR AREA. PLEASE REVIEW MANUFACTURER'S
 SPECIFICATIONS AND MAINTENANCE GUIDELINES. THE
 MANUFACTURER MAY RECOMMEND INSTALLATION OF A RECEPTOR
 AND DRAIN TO CONVEY HYDRAULIC FLUID AND OTHER LIQUID
 WASTES FROM THE COMPACTOR TO APPROVED PLACES OF
 DISPOSAL- SEC. 107.2.1 WPB. THE REVISED PLAN INDICATES
 KITTY LITTER WILL BE USED TO DISPOSE OF THE HYDRAULIC
 FLUID. KITTY LITTER DOES NOT APPEAR TO BE AN APPROVED
 METHOD FOR REMOVING HYDRAULIC FLUID FROM THE WASTE
 WATER. PLEASE SUBMIT THE REQUESTED MANUFACTURER'S
 SPECIFICATIONS FOR THE COMPACTOR AND REFER TO SEC.
 1003.1 FBC P- AN OIL INTERCEPTOR IS REQUIRED.
  
 18) FAILED ITEM C. P-200, P-803 & P-805:
 C) FAILED. P-805: SHOW THE LOCATION OF THE 6-INCH VENT
 STACK CONNECTION AT THE BASE OF THE 8-INCH SOIL STACK
 (SS/1)- SEC. 904.4 FBC P. THE 6-INCH VENT CONNECTION
 FOR THE 8-INCH SOIL STACK- SS/1 AT THE BASRE OF THE
 STACK IS NOT SHOWN ON P-805 OR P-200. ALSO MISSING IS
 THE REQUIRED VENT AT THE BASE OF SOIL STACK SS/2.
  
 19) FAILED. P-200, P-601, & P-801: PLEASE PROVIDE A
 SCHEDULE FOR THE DOMESTIC, FIRE, IRRIGATION, AND
 COOLING TOWER WATER SUPPLY BACKFLOW PREVENTERS SHOWN ON
 THE PLANS- SECS. C, D, & E WPB UTILITIES CROSS
 CONNECTION MANUAL. THE BF SCHEDULE ON P-601 INDICATES A
 DOUBLE CHECK VALVE BF FOR THE RESTAURANT POTABLE WATER
 HOWEVER AN RPZ IS REQUIRED PER THE WPB UTILITIES CROSS
 CONNECTION MANUAL
  
 21) FAILED A, B & E. P-501- FBC C P:
 A) FAILED. DETAIL 5- PROVIDE AN OVERFLOW DRAIN DETAIL-
 SECS. 1105.1 & 1108.1. AN OVERFLOW DRAIN WOULD BE
 DESIGNED TO HAVE THE INLET 2-INCHES ABOVE THE ROOF
 SURFACE. PLEASE REVIEW ZURN MANUFACTURER?S SPECS.
 B) FAILED. DETAIL 7- SHOW A MEANS OF THERMAL EXPANSION
 CONTROL FOR THE WATER HEATER- SEC. 607.3.THE EXPANSION
 TANK CONNECTION SHALL BE DOWNSTREAM OF THE CHECK VALVE.
 THE CURRENT LOCATION SHOWN IS UPSTREAM.
 E) FAILED. DETAIL 11- INDICATE HOW TEMPERED WATER WILL
 BE DELIVERED FROM THE LAVATORIES- SECS. 419.5 &
 607.1.2. THE WATER HEATER SHALL HAVE AN INTEGRAL ASSE
 1070 APPROVED TEMPERATURE LIMITING DEVICE IF USED AT
 THE LAVATORIES, OTHERWISE PROVIDE AN ASSE APPROVED
 MIXING VALVE FOR TEMPERED WATER DELIVERY.
  
 22) FAILED. P-208 & P-801: SHOW HW, HWR, & CW WATER
 SUPPLY BRANCH AND FIXTURE PIPING RUNS AND CONNECTIONS
 TO THE FIXTURES ON THE FLOOR PLAN, AND PROVIDE AN
 ENLARGED WATER RISER DRAWING- SECS.107.2.1 &
 107.3.5.1.3 WPB. REFER TO NOTE ON P-801. PROVIDE TRAP
 SEAL PROTECTION FOR THE FLOOR DRAINS- SEC. 1102.4.1 FBC
 P.
  
 23) FAILED. A- 101, 102, 103, 104, 108 & P-201, 202,
 203, 204, 208: LABEL THE BATHROOMS AND TOILETS ROOMS AS
 EITHER MALE, FEMALE, OR UNISEX- SEC. 403.2 FBC P.
 IDENTIFY THE LOCATIONS OF REQUIRED SERVICE SINKS AND
 DRINKING FOUNTAINS AND INCLUDE PIPING DETAILS- SEC.
 107.2.1 WPB. THE RESPONSE NARRATIVE INDICATES 1ST FLOOR
 DRINKING FOUNTAIN AT TARGET (01-303A) HOWEVER NO
 DRINKING FOUNTAIN SHOWN AT THAT LOCATION. REQUIRED
 DRINKING FOUNTAINS NOT SHOWN ON THE 4TH OR 8TH FLOORS.
 PLEASE NOTE THE DRINKING FOUINTAIN AT TARGET (02-128)
 ON A-102 IS PROTRUDING INTO THE CIRCULATION PATH- SEC.
 307.2 FBC ACC.
  
 24) FAILED. A-108: PROVIDE PLUMBING FIXTURE
 CALCULATIONS FOR THE 8TH FLOOR BATH AND TOILET ROOMS.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED NUMBER OF FIXTURES- TABLE 403.2 FBC P. PLEASE
 NOTE THAT DRINKING FOUNTAINS AND SERVICE SINKS ARE
 REQUIRED FIXTURES FOR A AND B OCCUPANCIES. IDENTIFY THE
 LOCATIONS AND PROVIDE PLUMBING PIPING DETAILS- SEC.
 107.2.1 WPB. DRINKING FOUNTAIN LOCATION AND PIPING
 DETAILS NOT PROVIDED.
  
 25) FAILED. A-660- A-108: ENLARGED DRAWINGS AND DETAILS
 FOR THE ACCESSIBLE 8TH FLOOR TERRACE SINGLE USER TOILET
 ROOMS NOT PROVIDED- SEC. 107.2.1 WPB. THE DIMENSIONS OF
 THE CLEAR FLOOR SPACES FOR THE FIXTURES NOT PROVIDED.
  
 26) FAILED. A-660 DETAILS 1 & 7: THE DIMENSIONS OF THE
 CLEAR FLOOR SPACES FOR THE WATER CLOSETS AND LAVATORIES
 ARE NOT SHOWN- SECS. 604.3 & 606.2 FBC ACC. DIMENSIONS
 SHOWN FOR THE WATER CLOSETS ARE INCORRECT. 60-INCHES
 WIDE X 56-INCHES DEEP CLEAR FLOOR SPACES REQUIRED.
  
 32) FAILED. DEFERRED SUBMITTALS: PLEASE PROVIDE A LIST
 OF DEFERRED SUBMITTALS INCLUDING, BUT NOT LIMITED TO
 WATER HEATERS, EXPANSION TANKS, RECIRCULATION PUMPS,
 SUMP PUMPS, MASTER AND POINT OF USE THERMOSTATIC MIXING
 VALVES, BACKFLOW PREVENTERS, TRAP PRIMERS, WATER HAMMER
 ARRESTORS, ACCESSIBLE PLUMBING FIXTURES, AND ROOF AND
 OVERFLOW DRAINS- SEC. 107.3.4.1 WPB. PLEASE PLACE THE
 LIST ON THE PLAN.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  