| 2022-08-24 15:04:24 | 2ND REVIEW FBC-2020 PLUMBING |
| | PERMIT- 21080907 |
| | 8/23/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLUMBING PLAN AUDIT. |
| | FAILED COMMENTS FROM THE 1ST AUDIT ARE PRINTED BELOW |
| | WITH ADDITIONALS NOTES IN CAP LETTERS FOR |
| | CLARIFICATION. PLEASE REVIEW THE COIMMENTS BELOW AND |
| | NOTE THE FOLLOWING: |
| | |
| | DUE TO A RECENT CHANGE IN PROCESS, THE POTABLE WATER |
| | BACKFLOW PREVENTER , GREASE INTERCEPTOR, AND OIL/SAND |
| | INTERCEPTOR PERMITS ARE REQUIRED TO BE SUBMITTED PRIOR |
| | TO ISSUANCE OF THE PRIMARY PERMIT. YOU CAN SUBMIT AN |
| | APPLICATION "TBD" (TO BE DETERMINED) IF YOU DO NOT HAVE |
| | A CONTRACTOR SELECTED BY EMAILING A COMPLETED PERMIT |
| | APPLICATION TO [email protected] . YOU WILL |
| | RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU |
| | MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE |
| | APPLICATION IS REQUIRED AT THIS TIME. WE RECOMMEND THAT |
| | YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME. AFTER |
| | YOU HAVE THE PERMIT(S) GENERATED, NOTIFY ME VIA EMAIL |
| | AND I WILL CHANGE THE REVIEW STATUS TO PASS. |
| | |
| | 2) FAILED ITEM 2B SHEET LS-101: BOH: B OCCUPANCY- 2 |
| | WATER CLOSETS AND 2 LAVATORIES ARE REQUIRED- 1 EACH FOR |
| | MALE AND FEMALE USE. PLEASE NOTE SEPARATE FACILITIES |
| | FOR MALE AND FEMALE USE ARE REQUIRED- SEE SEC. 403.2. |
| | ITEM #4 AND CORRECT THE CALCULATIONS. REVISED SHEET |
| | LS-100: THE CALCULATIONS ARE NOT BROKEN DOWN PER GENDER |
| | AND INDICATE A DEFICIENCY OF 1 WATER CLOSET AND 1 |
| | LAVATORY. |
| | |
| | 12) FAILED. P-200: COMMENT #11 IS ALSO APPLICABLE TO |
| | THE OIL INTERCEPTOR. PROVIDE INSTALLATION DETAILS AND |
| | NOTES ON THE PLAN, AND SUBMIT MANUFACTURERS |
| | INSTALLATION GUIDELINES FOR HIGH WATER AND HYDROSTATIC |
| | PRESSURE CONDITIONS, AND FOR VEHICULAR LOAD PROTECTION. |
| | THE NARRATIVE RESPONSE INDICATES FLOWABLE FILL DETAILS |
| | ON P-504, HOWEVER THE DETAILS THERE ARE FOR THE SCHIER |
| | INTERCEPTOR. DETAILS FOR THE ZURN OIL INTERCEPTOR WHICH |
| | IS SHOWN ON P-505 ARE NOT PROVIDED. |
| | |
| | 13) FAILED. P-200: PROVIDE RAIN WATER CISTERN |
| | INSTALLATION DETAILS AND NOTES ON THE PLAN AND SUBMIT |
| | MANUFACTURERS SPECIFICATIONS FOR THE TANK AND THE |
| | MANHOLE COVER. THE TANK AND COVER SHALL BE WATER TIGHT |
| | AND DESIGNED TO WITHSTAND HIGH WATER AND HYDROSTATIC |
| | PRESSURE CONDITIONS- SEC.- 309.2 FBC P AND SEC. 7.3.2 |
| | ASCE 24-14. BASED ON THE RESPONSE NARRATIVE PLEASE |
| | IDENTIFY THE WATER TANK SHOWN ON THE PLAN AS A CONCRETE |
| | RAIN CISTERN. PLEASE SHOW THE LOCATION OF THE MANHOLE |
| | ON THE PLAN AND PROVIDE EITHER NOTES OR DETAILS |
| | VERIFYING THE COVER WILL BE MINIMUM 24-INCHES IN |
| | DIAMTER, WATER TIGHT, AND LOCKABLE- SECS. 1301.9.6 AND |
| | 1303.12 FBC P. PLEASE NOTE THAT NON-POTABLE SIGNAGE IS |
| | REQUIRED PER SEC.- 1301.3. |
| | |
| | 15) FAILED. P-200: A WASTE RECEPTOR IS NOT SHOWN IN THE |
| | TRASH COMPACTOR AREA. PLEASE REVIEW MANUFACTURER'S |
| | SPECIFICATIONS AND MAINTENANCE GUIDELINES. THE |
| | MANUFACTURER MAY RECOMMEND INSTALLATION OF A RECEPTOR |
| | AND DRAIN TO CONVEY HYDRAULIC FLUID AND OTHER LIQUID |
| | WASTES FROM THE COMPACTOR TO APPROVED PLACES OF |
| | DISPOSAL- SEC. 107.2.1 WPB. THE REVISED PLAN INDICATES |
| | KITTY LITTER WILL BE USED TO DISPOSE OF THE HYDRAULIC |
| | FLUID. KITTY LITTER DOES NOT APPEAR TO BE AN APPROVED |
| | METHOD FOR REMOVING HYDRAULIC FLUID FROM THE WASTE |
| | WATER. PLEASE SUBMIT THE REQUESTED MANUFACTURER'S |
| | SPECIFICATIONS FOR THE COMPACTOR AND REFER TO SEC. |
| | 1003.1 FBC P- AN OIL INTERCEPTOR IS REQUIRED. |
| | |
| | 18) FAILED ITEM C. P-200, P-803 & P-805: |
| | C) FAILED. P-805: SHOW THE LOCATION OF THE 6-INCH VENT |
| | STACK CONNECTION AT THE BASE OF THE 8-INCH SOIL STACK |
| | (SS/1)- SEC. 904.4 FBC P. THE 6-INCH VENT CONNECTION |
| | FOR THE 8-INCH SOIL STACK- SS/1 AT THE BASRE OF THE |
| | STACK IS NOT SHOWN ON P-805 OR P-200. ALSO MISSING IS |
| | THE REQUIRED VENT AT THE BASE OF SOIL STACK SS/2. |
| | |
| | 19) FAILED. P-200, P-601, & P-801: PLEASE PROVIDE A |
| | SCHEDULE FOR THE DOMESTIC, FIRE, IRRIGATION, AND |
| | COOLING TOWER WATER SUPPLY BACKFLOW PREVENTERS SHOWN ON |
| | THE PLANS- SECS. C, D, & E WPB UTILITIES CROSS |
| | CONNECTION MANUAL. THE BF SCHEDULE ON P-601 INDICATES A |
| | DOUBLE CHECK VALVE BF FOR THE RESTAURANT POTABLE WATER |
| | HOWEVER AN RPZ IS REQUIRED PER THE WPB UTILITIES CROSS |
| | CONNECTION MANUAL |
| | |
| | 21) FAILED A, B & E. P-501- FBC C P: |
| | A) FAILED. DETAIL 5- PROVIDE AN OVERFLOW DRAIN DETAIL- |
| | SECS. 1105.1 & 1108.1. AN OVERFLOW DRAIN WOULD BE |
| | DESIGNED TO HAVE THE INLET 2-INCHES ABOVE THE ROOF |
| | SURFACE. PLEASE REVIEW ZURN MANUFACTURER?S SPECS. |
| | B) FAILED. DETAIL 7- SHOW A MEANS OF THERMAL EXPANSION |
| | CONTROL FOR THE WATER HEATER- SEC. 607.3.THE EXPANSION |
| | TANK CONNECTION SHALL BE DOWNSTREAM OF THE CHECK VALVE. |
| | THE CURRENT LOCATION SHOWN IS UPSTREAM. |
| | E) FAILED. DETAIL 11- INDICATE HOW TEMPERED WATER WILL |
| | BE DELIVERED FROM THE LAVATORIES- SECS. 419.5 & |
| | 607.1.2. THE WATER HEATER SHALL HAVE AN INTEGRAL ASSE |
| | 1070 APPROVED TEMPERATURE LIMITING DEVICE IF USED AT |
| | THE LAVATORIES, OTHERWISE PROVIDE AN ASSE APPROVED |
| | MIXING VALVE FOR TEMPERED WATER DELIVERY. |
| | |
| | 22) FAILED. P-208 & P-801: SHOW HW, HWR, & CW WATER |
| | SUPPLY BRANCH AND FIXTURE PIPING RUNS AND CONNECTIONS |
| | TO THE FIXTURES ON THE FLOOR PLAN, AND PROVIDE AN |
| | ENLARGED WATER RISER DRAWING- SECS.107.2.1 & |
| | 107.3.5.1.3 WPB. REFER TO NOTE ON P-801. PROVIDE TRAP |
| | SEAL PROTECTION FOR THE FLOOR DRAINS- SEC. 1102.4.1 FBC |
| | P. |
| | |
| | 23) FAILED. A- 101, 102, 103, 104, 108 & P-201, 202, |
| | 203, 204, 208: LABEL THE BATHROOMS AND TOILETS ROOMS AS |
| | EITHER MALE, FEMALE, OR UNISEX- SEC. 403.2 FBC P. |
| | IDENTIFY THE LOCATIONS OF REQUIRED SERVICE SINKS AND |
| | DRINKING FOUNTAINS AND INCLUDE PIPING DETAILS- SEC. |
| | 107.2.1 WPB. THE RESPONSE NARRATIVE INDICATES 1ST FLOOR |
| | DRINKING FOUNTAIN AT TARGET (01-303A) HOWEVER NO |
| | DRINKING FOUNTAIN SHOWN AT THAT LOCATION. REQUIRED |
| | DRINKING FOUNTAINS NOT SHOWN ON THE 4TH OR 8TH FLOORS. |
| | PLEASE NOTE THE DRINKING FOUINTAIN AT TARGET (02-128) |
| | ON A-102 IS PROTRUDING INTO THE CIRCULATION PATH- SEC. |
| | 307.2 FBC ACC. |
| | |
| | 24) FAILED. A-108: PROVIDE PLUMBING FIXTURE |
| | CALCULATIONS FOR THE 8TH FLOOR BATH AND TOILET ROOMS. |
| | PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND |
| | PROVIDED NUMBER OF FIXTURES- TABLE 403.2 FBC P. PLEASE |
| | NOTE THAT DRINKING FOUNTAINS AND SERVICE SINKS ARE |
| | REQUIRED FIXTURES FOR A AND B OCCUPANCIES. IDENTIFY THE |
| | LOCATIONS AND PROVIDE PLUMBING PIPING DETAILS- SEC. |
| | 107.2.1 WPB. DRINKING FOUNTAIN LOCATION AND PIPING |
| | DETAILS NOT PROVIDED. |
| | |
| | 25) FAILED. A-660- A-108: ENLARGED DRAWINGS AND DETAILS |
| | FOR THE ACCESSIBLE 8TH FLOOR TERRACE SINGLE USER TOILET |
| | ROOMS NOT PROVIDED- SEC. 107.2.1 WPB. THE DIMENSIONS OF |
| | THE CLEAR FLOOR SPACES FOR THE FIXTURES NOT PROVIDED. |
| | |
| | 26) FAILED. A-660 DETAILS 1 & 7: THE DIMENSIONS OF THE |
| | CLEAR FLOOR SPACES FOR THE WATER CLOSETS AND LAVATORIES |
| | ARE NOT SHOWN- SECS. 604.3 & 606.2 FBC ACC. DIMENSIONS |
| | SHOWN FOR THE WATER CLOSETS ARE INCORRECT. 60-INCHES |
| | WIDE X 56-INCHES DEEP CLEAR FLOOR SPACES REQUIRED. |
| | |
| | 32) FAILED. DEFERRED SUBMITTALS: PLEASE PROVIDE A LIST |
| | OF DEFERRED SUBMITTALS INCLUDING, BUT NOT LIMITED TO |
| | WATER HEATERS, EXPANSION TANKS, RECIRCULATION PUMPS, |
| | SUMP PUMPS, MASTER AND POINT OF USE THERMOSTATIC MIXING |
| | VALVES, BACKFLOW PREVENTERS, TRAP PRIMERS, WATER HAMMER |
| | ARRESTORS, ACCESSIBLE PLUMBING FIXTURES, AND ROOF AND |
| | OVERFLOW DRAINS- SEC. 107.3.4.1 WPB. PLEASE PLACE THE |
| | LIST ON THE PLAN. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |