| 2022-08-24 16:34:47 | 2ND REVIEW FBC-2020 FUEL GAS |
| | PERMIT- 21080907 |
| | 8/23/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | FAILED AUDIT COMMENTS #3 & 5 ARE LISTED WITH NOTES IN |
| | CAPS ADDED FOR CLARIFICATION. |
| | |
| | 3) FAILED. P-201- P-224: PLEASE PROVIDE NOTES AND |
| | DETAILS ON THE PLANS INDICATING THE LOCATIONS OF THE |
| | 2-HR FIRE RATED CHASE SPECIFIED ON THE DRAWING- SEC. |
| | 107.2.1 WPB. PLEASE NOTE THAT THE PIPING SHALL NOT |
| | PENETRATE INTO THE INTERIOR EXIT STAIRWAY- SEC. 1023.5 |
| | FBC B. THE LOCATIONS ARE NOW SHOWN HOWEVER THE |
| | NARRATIVE RESPONSE REFERENCES DETAIL 12 ON A-714. |
| | DETAIL 12 SHOWS A SHAFT ENCLOSURE USING THE CONCRETE |
| | SLAB AS ONE SIDE AND NOT A FOUR-SIDED FRAMED VERTICAL |
| | CHASE AS THE PLANS APPEAR TO INDICATE. THE DETAIL ALSO |
| | REFERENCES MEP DRAWINGS FOR PIPE SUPPORT METHOD. I WAS |
| | NOT ABLE TO LOCATE A PIPE SUPPORT DETAIL FOR THE 4-INCH |
| | SCHEDULE 40 METAL PIPES. |
| | |
| | 5) FAILED A & B. P-201 & P-802: THE DRAWINGS APPEAR TO |
| | SHOW THE LOW PRESSURE PIPE CONNECTION TO THE MAIN |
| | UPSTREAM OF THE 2 PSI PIPE CONNECTIONS TO THE |
| | GENERATORS. PLEASE REFER TO SECS. 5.5.1 & 7.9.7 NFPA |
| | 110 AND PROVIDE AN ENLARGED DETAIL FOR THE GAS SERVICE |
| | ENTRANCE. |
| | A) SHOW THE GENERATOR GAS PIPES AND SHUT OFF VALVES |
| | WILL BE CONNECTED ON THE SUPPLY SIDE OF THE MAIN VALVE |
| | AND WILL BE MARKED AS SUPPLYING EMERGENCY GENERATORS- |
| | SEC 7.9.7 NFPA 110. AND SEC. 409.3.3 FBC FG. |
| | B) SHOW THE LOCATION OF THE LOW PRESSURE GAS PIPE |
| | CONNECTION, SHUT OFF VALVE, AND PRESSURE REGULATOR- |
| | SEC. 410.2 FBC FG. |
| | IN RESPONSE TO THE COMMENTS THE NARRATIVE STATES A GAS |
| | SERVICE ENTRANCE DETAIL IS SHOWN ON P-201 OR P-802 |
| | HOWEVER THE DETAIL WAS NOT PROVIDED. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |