| 2022-07-18 11:29:19 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 21080907 |
| | 7/15/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLUMBING PLAN AUDIT. |
| | PLEASE REVIEW THE FOLLOWING COMMENTS. |
| | |
| | 1) SHEET G-000 OR G-001: PROVIDE ON THE PLAN A LIST OF |
| | REQUIRED ITEMS TO BE UNDER SEPARATE PERMITS INCLUDING, |
| | BUT NOT LIMITED TO- BACKFLOW PREVENTERS, FIRE LINE, |
| | FIRE SPRINKLERS, FIRE PUMP, GREASE INTERCEPTOR, |
| | OIL/SAND INTERCEPTOR, EMERGENCY AND STANDBY GENERATORS, |
| | IRRIGATION, TRASH COMPACTOR, AND THE TENANT BUILDOUTS. |
| | PLEASE NOTE EACH REQUIRED BACKFLOW SHALL BE SEPARATELY |
| | PERMITTED INCLUDING THE BF DEVICES FOR THE POTABLE |
| | WATER SERVICE, FIRE LINE, IRRIGATION, AND THE COOLING |
| | TOWER. |
| | DUE TO A RECENT CHANGE IN PROCESS, THE BACKFLOW, GREASE |
| | INTERCEPTOR, AND OIL/SAND INTERCEPTOR PERMITS ARE |
| | REQUIRED TO BE SUBMITTED PRIOR TO ISSUANCE OF THE |
| | PRIMARY PERMIT. YOU CAN SUBMIT AN APPLICATION "TBD" (TO |
| | BE DETERMINED) IF YOU DO NOT HAVE A CONTRACTOR SELECTED |
| | BY EMAILING A COMPLETED PERMIT APPLICATION TO |
| | [email protected] . YOU WILL RECEIVE INSTRUCTIONS |
| | TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND |
| | PAY FEES AT A FUTURE DATE, BUT THE APPLICATION IS |
| | REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES |
| | AND UPLOAD PLANS AT THE SAME TIME. AFTER YOU HAVE THE |
| | PERMIT(S) GENERATED, NOTIFY ME VIA EMAIL AND I WILL |
| | CHANGE THE REVIEW STATUS TO PASS. |
| | |
| | 2) SHEET LS-101: THE PLUMBING FIXTURE CALCULATIONS ARE |
| | NOT IN COMPLIANCE WITH TABLE 403.2 FBC P. |
| | A) RETAIL A & B: M OCCUPANCIES- 2 WATER CLOSETS AND 2 |
| | LAVATORIES ARE REQUIRED- 1 EACH FOR MALE AND FEMALE |
| | USE. PLEASE NOTE SEPARATE FACILITIES FOR MALE AND |
| | FEMALE USE ARE REQUIRED- SEE SEC. 403.2 ITEM #3 AND |
| | CORRECT THE CALCULATIONS. |
| | B) BOH: B OCCUPANCY- 2 WATER CLOSETS AND 2 LAVATORIES |
| | ARE REQUIRED- 1 EACH FOR MALE AND FEMALE USE. PLEASE |
| | NOTE SEPARATE FACILITIES FOR MALE AND FEMALE USE ARE |
| | REQUIRED- SEE SEC. 403.2. ITEM #4 AND CORRECT THE |
| | CALCULATIONS. |
| | C) READING ROOM: A OCCUPANCY- 2 WATER CLOSETS AND 2 |
| | LAVATORIES ARE REQUIRED- 1 EACH FOR MALE AND FEMALE. |
| | PLEASE NOTE SEPARATE FACILITIES FOR MALE AND FEMALE USE |
| | ARE REQUIRED- SEE SEC. 403.2. DRINKING FOUNTAINS AND |
| | SERVICE SINKS ARE ALSO REQUIRED FIXTURES FOR THE |
| | READING ROOM. PLEASE CORRECT THE CALCULATIONS. |
| | |
| | 3) SHEETS P-200 & P-805: THE COOLING TOWER DRAIN LINE |
| | IS LABELED A SANITARY LINE HOWEVER UNCONTAMINATED |
| | COOLING WATER IS PROHIBITED FROM DISCHARGING INTO THE |
| | CITY SANITARY SYSTEM PER SEC. 90-126 (5) WPB CODE OR |
| | ORDINANCES. PLEASE CONTACT THE WPB UTILITIES DEPT. FOR |
| | ASSISTANCE AT 561-494-1074. |
| | |
| | 4) P-200: THE COOLING TOWER DRAIN LINE IS LABELED BOTH |
| | 6-INCH AND 8-INCH ON THE PLAN- PLEASE CORRECT- SEC. |
| | 107.2.1 WPB. |
| | |
| | 5) P-200 & P-805: SHOW THE LOCATION OF THE FUTURE |
| | SANITARY LINE FOR RETAIL B ON SHEET P-805- SEC. 107.2.1 |
| | WPB. |
| | |
| | 6) P-200: SHOW THE TRENCH DRAIN PIPE POINT OF |
| | CONNECTION TO AN APPROVED PLACE OF DISPOSAL- SEC. 301.3 |
| | FBC P. |
| | |
| | 7) P-200 & P-805: PLEASE IDENTIFY THE WHAT FIXTURE OR |
| | EQUIPMENT DRAINAGE IS BEING CONVEYED FROM THE HUB DRAIN |
| | TO THE OIL INTERCEPTOR- SEC. 1003.4 FBC P. PLEASE SEE |
| | SEC. 1003.4.2.2 FBC P AND CLARIFY THE NEED FOR THE |
| | INTERCEPTOR AND THE CAPACITY WAS CALCULATED. WILL |
| | VEHICLES BE REPAIRED OR WASHED IN THE DOCK AREA? |
| | |
| | 8) P-200: INDICATE THE TYPES OF SLEEVES FOR THE GREASE |
| | WASTE AND SANITARY LINE AND SUBMIT MANUFACTURERS |
| | SPECIFICATIONS AND INSTALLATION MANUAL FOR THE HEAT |
| | TRACE SYSTEM- SEC. 305.2 FBC P & SEC. 107.2.1 WPB. |
| | CLARIFY HOW THE SYSTEM WILL BE MADE WATER TIGHT PER THE |
| | NOTE ON THE PLAN- SEC. 309.2 FBC P. |
| | |
| | 9) P-200: THE SLEEVE NOTE IN THE LOADING DOCK CALLS OUT |
| | A 6-INCH SANITARY HOWEVER THE ARROW POINTS TO AN |
| | 8-INCH- PLEASE CLARIFY- SEC. 107.2.1 WPB. |
| | |
| | 10) P-200: THE BUILDING IS BEING CONSTRUCTED IN AN AE |
| | FLOOD HAZARD ZONE. REFER TO SEC. 309.2 FBC P FLOOD |
| | HAZARD AND SEC. 7.3 ASCE 24-14: THE PLUMBING SYSTEMS, |
| | EQUIPMENT, FIXTURES AND OTHER COMPONENTS SYSTEM SHALL |
| | BE INSTALLED ABOVE THE DESIGN FLOOD ELEVATION HEIGHT, |
| | OR MEET THE EXCEPTION UNDER 309.2. PROVIDE NOTES ON |
| | G-011 THAT ARE APPLICABLE TO THE PLUMBING SYSTEMS. |
| | A) P-200: PROVIDE NOTES AND/OR DETAILS ON THE PLAN |
| | SHOWING COMPLIANCE WITH 7.3.1 ASCE 24-14: UNDERGROUND |
| | PIPING AND PLUMBING SYSTEMS SHALL BE BURIED TO A DEPTH |
| | SUFFICIENT TO PREVENT MOVEMENT, SEPARATION, OR LOSS DUE |
| | TO FLOODING AND EROSION UNDER DESIGN FLOOD CONDITIONS. |
| | B) P-200: OPENINGS IN THE PLUMBING SYSTEMS BELOW THE |
| | DESIGN FLOOD ELEVATION HEIGHT SHALL BE PROTECTED WITH |
| | AUTOMATIC BACKWATER VALVES. SHOW COMPLIANCE WITH NOTES |
| | AND DETAILS ON THE PLANS. IT APPEARS THAT THE TRENCH |
| | DRAIN AND HUB DRAIN OPENINGS IN THE LOADING DOCK AREA, |
| | AND THE FLOOR DRAIN IN THE PUMP ROOM ARE BELOW THE |
| | HEIGHT AND WILL REQUIRE THE VALVES- SEC. 714.1 FBC P. |
| | |
| | 11) P-200: PROVIDE NOTES TO INDICATE THE GREASE |
| | INTERCEPTOR AND SOLIDS INTERCEPTOR WILL BE INSTALLED IN |
| | A WATER TIGHT CONCRETE VAULT WITH SEALED, WATER TIGHT |
| | MANHOLE COVERS- SEC. 309.2 FBC P AND SEC. 7.3.2 ASCE |
| | 24-14. PROVIDE DETAILS ON THE PLAN AND MARKUP ALL |
| | APPLICABLE INSTALLATION DETAILS SHOWN ON P-504 |
| | INCLUDING THE INSTALLATION OF A MINIMUM 8-INCH SLAB ON |
| | TOP OF THE VAULT. |
| | |
| | 12) P-200: COMMENT #11 IS ALSO APPLICABLE TO THE OIL |
| | INTERCEPTOR. PROVIDE INSTALLATION DETAILS AND NOTES ON |
| | THE PLAN, AND SUBMIT MANUFACTURERS INSTALLATION |
| | GUIDELINES FOR HIGH WATER AND HYDROSTATIC PRESSURE |
| | CONDITIONS, AND FOR VEHICULAR LOAD PROTECTION. |
| | |
| | 13) P-200: PROVIDE RAIN WATER CISTERN INSTALLATION |
| | DETAILS AND NOTES ON THE PLAN AND SUBMIT MANUFACTURERS |
| | SPECIFICATIONS FOR THE TANK AND THE MANHOLE COVER. THE |
| | TANK AND COVER SHALL BE WATER TIGHT AND DESIGNED TO |
| | WITHSTAND HIGH WATER AND HYDROSTATIC PRESSURE |
| | CONDITIONS- SEC.- 309.2 FBC P AND SEC. 7.3.2 ASCE |
| | 24-14. |
| | |
| | 14) P-200: VERIFY THE PUMPS HAVE ADEQUATE SEALS TO |
| | RESIST FLOOD WATER INTRUSION- SEC. 309.2 AND SEC. 7.3.3 |
| | ASCE 24-14. |
| | |
| | 15) P-200: A WASTE RECEPTOR IS NOT SHOWN IN THE TRASH |
| | COMPACTOR AREA. PLEASE REVIEW MANUFACTURER'S |
| | SPECIFICATIONS AND MAINTENANCE GUIDELINES. THE |
| | MANUFACTURER MAY RECOMMEND INSTALLATION OF A RECEPTOR |
| | AND DRAIN TO CONVEY HYDRAULIC FLUID AND OTHER LIQUID |
| | WASTES FROM THE COMPACTOR TO APPROVED PLACES OF |
| | DISPOSAL- SEC. 107.2.1 WPB. |
| | 16) P-201: THERE APPEARS TO BE A DRAIN PIPE PENETRATING |
| | INTO EXIT STAIR B WHICH IS PROHIBITED PER SEC. 1023.5 |
| | FBC B. |
| | |
| | 17) P-805: THE 6-INCH SANITARY DRAIN PIPES APPEAR TO BE |
| | MISLABELED AS COOLING DRAINS WITH NOTES AT THE 4TH AND |
| | 6TH FLOORS. ARE THESE NOTES MEANT TO INDICATE |
| | CONDENSATE DRAINS? FOR CLARITY PLEASE PROVIDE A |
| | SEPARATE CONDENSATE DISPOSAL RISER DRAWING, AND NOTE |
| | THAT CONDENSATE SHALL NOT DRAIN INTO THE SANITARY |
| | SYSTEM- SEC. 90-126 (5) WPB CODE OF ORDINANCES. |
| | |
| | 18) P-200, P-803 & P-805: |
| | A) CORRECT THE 839 DFU TOTAL FOR THE 8-INCH (SS/3) |
| | SHOWN ON P-803. THE RISER ON P-805 SHOWS 155 DFU'S FOR |
| | THE PIPE- SEC. 107.2.1 WPB. |
| | B) HD-B IS MISLABELED AS THE 8-INCH COOLING TOWER DRAIN |
| | ON P-200. PLEASE CORRECT- SEC. 107.2.1 WPB. |
| | C) P-805: SHOW THE LOCATION OF THE 6-INCH VENT STACK |
| | CONNECTION AT THE BASE OF THE 8-INCH SOIL STACK (SS/1)- |
| | SEC. 904.4 FBC P. |
| | D) P-803: THE 6-INCH AND 4-INCH RELIEF VENTS NOTED ARE |
| | INCORRECTLY SIZED PER SEC. 908.1 FBC P. THE VENTS SHALL |
| | BE 3-INCH AND 4-INCH IN SIZE. PLEASE SHOW THE RELIEF |
| | VENT PIPE RUNS ON THE RISER. |
| | E) P-803: A 3-INCH RELIEF VENT IS REQUIRED ON LEVEL 5 |
| | FOR THE 4-INCH STACK- SEC. 908.1 AND 908.2. |
| | F) P-803: SHOW THE LOCATIONS OF THE REQUIRED 6-INCH |
| | RELIEF VENTS FOR THE 6-INCH STACK (SS/1)- SEC. 908.1 & |
| | 908.2. |
| | |
| | 19) P-200, P-601, & P-801: PLEASE PROVIDE A SCHEDULE |
| | FOR THE DOMESTIC, FIRE, IRRIGATION, AND COOLING TOWER |
| | WATER SUPPLY BACKFLOW PREVENTERS SHOWN ON THE PLANS- |
| | SECS. C, D, & E WPB UTILITIES CROSS CONNECTION MANUAL. |
| | |
| | 20) P-200 & P-804: THE STORM RISER DOES NOT SHOW THE |
| | VERTICAL RW DRAIN CONNECTIONS TO HORIZONTAL UNDERGROUND |
| | DRAINS INCLUDING THE 12-INCH RW CONNECTION TO THE MAIN |
| | 15-INCH STORM DRAIN- SEC. 1101.2 FBC P. |
| | |
| | 21) P-501- FBC C P: |
| | A) DETAIL 5- PROVIDE AN OVERFLOW DRAIN DETAIL- SECS. |
| | 1105.1 & 1108.1. |
| | B) DETAIL 7- SHOW A MEANS OF THERMAL EXPANSION CONTROL |
| | FOR THE WATER HEATER- SEC. 607.3. |
| | C) DETAIL 7- THE HWR LINE SHALL MAKE CONNECTION INTO |
| | THE THERMOSTATIC MIXING VALVE- SEC. 607.2.2 |
| | D) DETAIL 11- A DEDICATED SHUT OFF VALVE IS REQUIRED |
| | FOR SUPPLY LINE TO THE WATER HEATER- SEC. 503.1. |
| | E) DETAIL 11- INDICATE HOW TEMPERED WATER WILL BE |
| | DELIVERED FROM THE LAVATORIES- SECS. 419.5 & 607.1.2. |
| | |
| | 22) P-208 & P-801: SHOW HW, HWR, & CW WATER SUPPLY |
| | BRANCH AND FIXTURE PIPING RUNS AND CONNECTIONS TO THE |
| | FIXTURES ON THE FLOOR PLAN, AND PROVIDE AN ENLARGED |
| | WATER RISER DRAWING- SECS.107.2.1 & 107.3.5.1.3 WPB. |
| | REFER TO NOTE ON P-801. |
| | |
| | 23) A- 101, 102, 103, 104, 108 & P-201, 202, 203, 204, |
| | 208: LABEL THE BATHROOMS AND TOILETS ROOMS AS EITHER |
| | MALE, FEMALE, OR UNISEX- SEC. 403.2 FBC P. IDENTIFY THE |
| | LOCATIONS OF REQUIRED SERVICE SINKS AND DRINKING |
| | FOUNTAINS AND INCLUDE PIPING DETAILS- SEC. 107.2.1 WPB. |
| | |
| | 24) A-108: PROVIDE PLUMBING FIXTURE CALCULATIONS FOR |
| | THE 8TH FLOOR BATH AND TOILET ROOMS. PROVIDE A SCHEDULE |
| | THAT INDICATES THE REQUIRED AND PROVIDED NUMBER OF |
| | FIXTURES- TABLE 403.2 FBC P. PLEASE NOTE THAT DRINKING |
| | FOUNTAINS AND SERVICE SINKS ARE REQUIRED FIXTURES FOR A |
| | AND B OCCUPANCIES. IDENTIFY THE LOCATIONS AND PROVIDE |
| | PLUMBING PIPING DETAILS- SEC. 107.2.1 WPB. |
| | |
| | 25) A-660- A-108: ENLARGED DRAWINGS AND DETAILS FOR THE |
| | ACCESSIBLE 8TH FLOOR TERRACE SINGLE USER TOILET ROOMS |
| | NOT PROVIDED- SEC. 107.2.1 WPB. |
| | |
| | 26) A-660 DETAILS 1 & 7: THE DIMENSIONS OF THE CLEAR |
| | FLOOR SPACES FOR THE WATER CLOSETS AND LAVATORIES ARE |
| | NOT SHOWN- SECS. 604.3 & 606.2 FBC ACC. |
| | |
| | 27) A-660 DETAILS 1 & 7: THE DIMENSIONS OF THE TURNING |
| | CIRCLES NOT SHOWN- SEC. 304.3 FBC ACC. |
| | |
| | 28) A-660 & G-009- MISSING OR INCORRECT ACCESSIBLE |
| | BATHROOM DETAILS PER FBC ACC. |
| | A) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE |
| | WALLS- SEC. 604.2. |
| | B) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO |
| | THE REFLECTIVE SURFACES- SEC. 603.3 |
| | C) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| | BARS FOR THE WATER CLOSETS- SECS. 604.5 & 609.4, |
| | FIGURES 604. NOTE: MEASUREMENTS SHOWN ARE NOT TO THE |
| | TOPS OF THE GRIPPING SURFACES. |
| | D) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SEC. |
| | 606.2 |
| | E) THE ACCESSIBLE TRANSFER SHOWERS SHALL BE 36 X 36 |
| | INCHES CLEAR INSIDE DIMENSIONS- SEC. 608.2.1 WPB. THE |
| | PLAN SHOWS 48-INCH WIDE SHOWERS THAT ARE NOT IN |
| | COMPLIANCE. |
| | F) SHOW THE CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS |
| | FOR THE SHOWER- SEC. 608.2.1 |
| | G) SHOW THE LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF |
| | GRAB BARS FOR THE ACCESSIBLE SHOWER- SECS. 608.3 AND |
| | 608.3.1 |
| | H) LOCATIONS OF CONTROLS, FAUCETS, AND SHOWER SPRAYS IN |
| | THE SHOWERS- SEC. 608.5.1. |
| | I) SHOWER SPRAY UNIT SPECIFICATIONS PER SEC. 608.6. |
| | J) ENLARGED ACCESSIBLE SHOWER SEAT DETAILS- SECS. |
| | 610.3- 610.3.2. |
| | |
| | 29) A-811: ACCESSIBLE VANITY SINK KNEE AND TOE SPACE |
| | CLEARANCES NOT SHOWN IN ACCORDANCE WITH SECS. & FIGURES |
| | 306.2 & 306.3 FBC ACC. |
| | |
| | 30) P-224: THE FCU 24-02 IS PROHIBITED FROM BEING |
| | INSTALLED IN THE INTERIOR EXIT STAIRWAY- SEC. 1023.5 |
| | FBC P. |
| | |
| | 31) PROVIDE A CONDENSATE DISPOSAL RISER- SEC. |
| | 107.3.5.1.3 WPB. |
| | |
| | 32) DEFERRED SUBMITTALS: PLEASE PROVIDE A LIST OF |
| | DEFERRED SUBMITTALS INCLUDING, BUT NOT LIMITED TO WATER |
| | HEATERS, EXPANSION TANKS, RECIRCULATION PUMPS, SUMP |
| | PUMPS, MASTER AND POINT OF USE THERMOSTATIC MIXING |
| | VALVES, BACKFLOW PREVENTERS, TRAP PRIMERS, WATER HAMMER |
| | ARRESTORS, ACCESSIBLE PLUMBING FIXTURES, AND ROOF AND |
| | OVERFLOW DRAINS- SEC. 107.3.4.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |