 1ST CYCLE MECHANICAL AUDIT
  
  
 1) REVISE THE ENERGY CALCULATIONS TO LIST THE NUMBER OF
 STORIES IN THIS BUILDING. IT CURRENTLY STATES THE
 NUMBER OF STORIES AS 1. FBC 107.2.1
  
 2) THE ENERGY CALCULATIONS, PAGE 10 OF 64, LISTS A
 ERU-3. SHEET M-700 OF THE DRAWINGS DOES NOT LIST A
 ERU-3. EXPLAIN. FBC 107.2.1
  
 3) THERE SEEMS TO BE SEVERAL FCU?S LISTED ON THE ENERGY
 CALCULATIONS, BUT THEY ARE MISSING FROM THE FCU
 SCHEDULE ON SHEET M-701. EXPLAIN. FBC 107.2.1
  