| 2022-07-18 13:36:54 | 1ST REVIEW FBC-2020 FUEL GAS |
| | PERMIT- 21080907 |
| | 7/18/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | GAS AUDIT. PLEASE REVIEW THE COMMENTS BELOW. |
| | |
| | 1) SHEET P-802: THE 2 PSI PIPE SIZING TABLE 402.4(4) |
| | SPECIFIED IS A LOW-PRESSURE TABLE. PLEASE REMOVE AND |
| | REPLACE WITH EITHER TABLE 402.4(5) OR 402.4(6) FBC FG. |
| | |
| | 2) P-802: USING THE LOW-PRESSURE SIZING TABLE 402.4(2) |
| | SPECIFIED, THE 2-INCH PIPE IS LIMITED TO 546 CFH AT 400 |
| | FT. TOTAL DEVELOPED LENGTH. PLEASE INCREASE THE SIZE OF |
| | THE PIPE TO 4-INCH PER THE TABLE. |
| | |
| | 3) P-201- P-224: PLEASE PROVIDE NOTES AND DETAILS ON |
| | THE PLANS INDICATING THE LOCATIONS OF THE 2-HR FIRE |
| | RATED CHASE SPECIFIED ON THE DRAWING- SEC. 107.2.1 WPB. |
| | PLEASE NOTE THAT THE PIPING SHALL NOT PENETRATE INTO |
| | THE INTERIOR EXIT STAIRWAY- SEC. 1023.5 FBC B. |
| | |
| | 4) P-225 & P-802: SEPARATE PERMITS ARE REQUIRED FOR THE |
| | GENERATORS. PLACE NOTES ON THE PLANS ACCORDINGLY- SEC. |
| | 105.1 & 107.2.1 WPB. PLEASE CLARIFY IF THE GENERATORS |
| | ARE FOR STANDBY AND EMERGENCY USE AND INDICATE WHICH |
| | BUILDING SYSTEM LOADS ARE BEING SUPPLIED BY THE UNITS- |
| | SECS. 403.8.3 & 403.4.8.4 FBC B. |
| | |
| | 5) P-201 & P-802: THE DRAWINGS APPEAR TO SHOW THE LOW |
| | PRESSURE PIPE CONNECTION TO THE MAIN UPSTREAM OF THE 2 |
| | PSI PIPE CONNECTIONS TO THE GENERATORS. PLEASE REFER TO |
| | SECS. 5.5.1 & 7.9.7 NFPA 110 AND PROVIDE AN ENLARGED |
| | DETAIL FOR THE GAS SERVICE ENTRANCE. |
| | A) SHOW THE GENERATOR GAS PIPES AND SHUT OFF VALVES |
| | WILL BE CONNECTED ON THE SUPPLY SIDE OF THE MAIN VALVE |
| | AND WILL BE MARKED AS SUPPLYING EMERGENCY GENERATORS- |
| | SEC 7.9.7 NFPA 110. AND SEC. 409.3.3 FBC FG. |
| | B) SHOW THE LOCATION OF THE LOW PRESSURE GAS PIPE |
| | CONNECTION, SHUT OFF VALVE, AND PRESSURE REGULATOR- |
| | SEC. 410.2 FBC FG. |
| | |
| | 6) SUBMIT COMPLETE SPECIFICATIONS FOR THE GENERATORS- |
| | SEC. 616.1 FBC FG. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |