Plan Review Notes
Plan Review Notes For Permit 21080907
Permit Number 21080907
Review Stop G
Sequence Number 1
Notes
Date Text
2022-07-18 13:36:541ST REVIEW FBC-2020 FUEL GAS
 PERMIT- 21080907
 7/18/2022
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 GAS AUDIT. PLEASE REVIEW THE COMMENTS BELOW.
  
 1) SHEET P-802: THE 2 PSI PIPE SIZING TABLE 402.4(4)
 SPECIFIED IS A LOW-PRESSURE TABLE. PLEASE REMOVE AND
 REPLACE WITH EITHER TABLE 402.4(5) OR 402.4(6) FBC FG.
  
 2) P-802: USING THE LOW-PRESSURE SIZING TABLE 402.4(2)
 SPECIFIED, THE 2-INCH PIPE IS LIMITED TO 546 CFH AT 400
 FT. TOTAL DEVELOPED LENGTH. PLEASE INCREASE THE SIZE OF
 THE PIPE TO 4-INCH PER THE TABLE.
  
 3) P-201- P-224: PLEASE PROVIDE NOTES AND DETAILS ON
 THE PLANS INDICATING THE LOCATIONS OF THE 2-HR FIRE
 RATED CHASE SPECIFIED ON THE DRAWING- SEC. 107.2.1 WPB.
 PLEASE NOTE THAT THE PIPING SHALL NOT PENETRATE INTO
 THE INTERIOR EXIT STAIRWAY- SEC. 1023.5 FBC B.
  
 4) P-225 & P-802: SEPARATE PERMITS ARE REQUIRED FOR THE
 GENERATORS. PLACE NOTES ON THE PLANS ACCORDINGLY- SEC.
 105.1 & 107.2.1 WPB. PLEASE CLARIFY IF THE GENERATORS
 ARE FOR STANDBY AND EMERGENCY USE AND INDICATE WHICH
 BUILDING SYSTEM LOADS ARE BEING SUPPLIED BY THE UNITS-
 SECS. 403.8.3 & 403.4.8.4 FBC B.
  
 5) P-201 & P-802: THE DRAWINGS APPEAR TO SHOW THE LOW
 PRESSURE PIPE CONNECTION TO THE MAIN UPSTREAM OF THE 2
 PSI PIPE CONNECTIONS TO THE GENERATORS. PLEASE REFER TO
 SECS. 5.5.1 & 7.9.7 NFPA 110 AND PROVIDE AN ENLARGED
 DETAIL FOR THE GAS SERVICE ENTRANCE.
 A) SHOW THE GENERATOR GAS PIPES AND SHUT OFF VALVES
 WILL BE CONNECTED ON THE SUPPLY SIDE OF THE MAIN VALVE
 AND WILL BE MARKED AS SUPPLYING EMERGENCY GENERATORS-
 SEC 7.9.7 NFPA 110. AND SEC. 409.3.3 FBC FG.
 B) SHOW THE LOCATION OF THE LOW PRESSURE GAS PIPE
 CONNECTION, SHUT OFF VALVE, AND PRESSURE REGULATOR-
 SEC. 410.2 FBC FG.
  
 6) SUBMIT COMPLETE SPECIFICATIONS FOR THE GENERATORS-
 SEC. 616.1 FBC FG.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  