| 2021-12-27 15:32:10 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) THERE ARE INDICATIONS ON THE CIVIL SHEETS OF |
| | UNDEGROUND FIRE LINES, INCLUDING THE FDC & DDCV. |
| | |
| | ALL FIRE LINE UNDERGROUND WORK INCLUDING THE FDC & DDCV |
| | SHALL INSTALLED PER NFPA 24 AND UNDER SEPARATE PERMIT |
| | AND SHOP DRAWINGS . |
| | |
| | PLEASE REVIEW AND PROVIDE A NOTE OF ACKNOWLEDGEMENT ON |
| | THE CIVIL SHEET C - 400. |
| | |
| | |
| | |
| | 2) THERE ARE INDICATIONS OF AN ELECTIRC FIRE PUMP AND A |
| | GENERATOR; HOWEVER, THERE IS NO INDICATON THAT THE |
| | ELECTRIC FIRE PUMP WILL BE POWERED BY THE GENERATOR IN |
| | THE EVENT OF LOSS OF POWER. |
| | |
| | PER NFPA 20 |
| | |
| | 9.3 ALTERNATE POWER. |
| | 9.3.1 EXCEPT FOR AN ARRANGEMENT DESCRIBED IN 9.3.3, AT |
| | LEAST |
| | ONE ALTERNATE SOURCE OF POWER SHALL BE PROVIDED WHERE |
| | THE |
| | HEIGHT OF THE STRUCTURE IS BEYOND THE PUMPING CAPACITY |
| | OF THE |
| | FIRE DEPARTMENT APPARATUS. |
| | 9.3.2* OTHER SOURCES. EXCEPT FOR AN ARRANGEMENT |
| | DESCRIBED IN |
| | 9.3.3, AT LEAST ONE ALTERNATE SOURCE OF POWER SHALL BE |
| | PROVIDED |
| | WHERE THE NORMAL SOURCE IS NOT RELIABLE. |
| | 9.3.3 AN ALTERNATE SOURCE OF POWER FOR THE PRIMARY FIRE |
| | PUMP |
| | SHALL NOT BE REQUIRED WHERE A BACKUP ENGINE-DRIVEN FIRE |
| | PUMP, |
| | BACKUP STEAM TURBINE-DRIVEN FIRE PUMP, OR BACKUP |
| | ELECTRIC |
| | MOTOR?DRIVEN FIRE PUMP WITH INDEPENDENT POWER SOURCE |
| | MEETING |
| | 9.2.2 IS INSTALLED IN ACCORDANCE WITH THIS STANDARD. |
| | |
| | PLEASE REVIEW AND PROVIDE A NOTE OF ACKOWLEDGEMENT TO |
| | COMPLY ON THE LS, FP & GENERATOR SHEETS |
| | |
| | |
| | 3) THERE ARE NO INDICATIONS OF A BDA SYSTEM |
| | |
| | NFPA 1, CHAPTER 11, BUILDING SERVICES; 11.10 TWO-WAY |
| | RADIO ENHANCEMENT SERVICES. |
| | |
| | 11.10.1 IN ALL NEW AND EXISTING BUILDINGS, MINIMUM |
| | RADIO SIGNAL STRENGTH FOR FIRE DEPARTMENT |
| | COMMUNICATIONS SHALL BE MAINTAINED AT A LEVEL |
| | DETERMINED BY THE AHJ. |
| | |
| | PLEASE CONTACT MARK FILLA, PALM BEACH COUNTY PUBLIC |
| | SAFETY RADIO SYSTEMS MANAGER, AS OUR RADIOS OPERATE ON |
| | THEIR SYSTEM FOR DETAILED RADIO FREQUENCY AND |
| | INSTALLATION INSTRUCTIONS. |
| | |
| | THERE IS NO WAY TO DETERMINE IF YOUR BUILDING WOULD |
| | NEED IT OR NOT WITHOUT PROPER TESTING. |
| | |
| | SHOULD YOUR BUILDING NOT PASS THE TESTING/SURVEY, AN |
| | AMPLIFICATION SYSTEM WOULD BE REQUIRED. |
| | |
| | SHOULD YOUR BUILDING PASS THE TESTING/SURVEY I WOULD |
| | COME IN WITH OUR PORTABLE RADIOS AND CONDUCT AN |
| | OPERATIONAL TEST TO CONFIRM. IF THE PORTABLE RADIO TEST |
| | FAILS AN AMPLIFICATION SYSTEM IS REQUIRED. |
| | |
| | THE OWNER/CONTRACTOR WOULD BE RESPONSIBLE TO CONDUCT |
| | THE TESTING/SURVEY BY A QUALIFIED THIRD PARTY. |
| | |
| | A BDA PERMIT IS REQUIRED SEPARATE FROM ANY OTHER |
| | PERMIT. |
| | |
| | |
| | PLEASE REVIEW AND PROVIDE A NOTE OF ACKOWLEDGEMENT TO |
| | COMPLY ON THE LS SHEET LS - 101. |
| | |
| | |
| | |
| | 4) THERE IS NO RATIONAL ANALYSIS DOCUMENT THAT COULD BE |
| | REVIEWED FOR THE SMOKE CONTROL SYSTEM(S) APPLICABLE |
| | SEQUENCE OF OPERATION. |
| | |
| | THE SMOKE CONTROL SHEETS WERE REVIEWED; HOWEVER, THE |
| | INFORMATION PROVIDED ON THOSE SHEETS DOES NOT PROVIDE |
| | CLEAR INDICATIONS IN A LOGICAL ORDER. |
| | |
| | PLEASE REVIEW AND PROVIDE A DETAILED DOCUMENT FOR |
| | REVIEW. |
| | |
| | |
| | |
| | 5) ON THE LIFE SAFETY SHEETS FLOORS 1 THRU 3 , THERE |
| | DOES NOT APPEAR TO BE AN EXIT SIGN WITHIN THE THE FSV |
| | OVER THE EXIT DOOR TO LEADING TO THE STAIRWELL. |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | |
| | 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |