| Date |
Text |
| 2022-07-25 08:07:34 | MICHAEL PETERSON |
| | ELECTRICAL PLANS EXAMINER |
| | [email protected] |
| | 561-805-6746 |
| | |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | MICHAEL PETERSON |
| | ELECTRICAL PLANS EXAMINER |
| | [email protected] |
| | 561-805-6746 |
| | |
| | |
| | 1) PLEASE CORRECT INCONSISTENT TRANSFORMER RATING AND |
| | OVERCURRENT PROTECTION BETWEEN PANELS 2M5 AND 4M5 ON |
| | SHEET E 704. IN ADDITION, FED FROM NOMENCLATURE, IS |
| | INCORRECT ON PANEL SCHEDULE 2M5. FBC 107.2 |
| | 2) THERE APPEARS TO BE DISCREPANCIES IN THE ONE LINE |
| | RISER DIAGRAM DETAILING, ATS ELEVATOR PARKING, NORMAL |
| | FEED, FROM MAIN 4 ON SHEET E 503, MAIN 1 ON SHEET E 501 |
| | AND DB 1 SHEET E 703. PLEASE CORRECT AS APPLICABLE. FBC |
| | 107.2 |
| | 3) RISER DIAGRAM DETAILS 250 Y CONDUCTORS FED FROM 800 |
| | AMP BREAKER FOR ATS ELEV-PARKING ON SHEET E-501. PLEASE |
| | CORRECT AS APPLICABLE. NEC 215.5 |
| | 4) RISER DIAGRAM ON SHEET E-503 DETAILS A 600 AMP RATED |
| | TRANSFER SWITCH, ATS-O-RESTAURANT, FED FROM A 800 AMP |
| | BREAKER FROM MAIN 2 ON SHEET E-501 AND A 600 AMP |
| | BREAKER FROM ESB SWITCHBOARD, ON SHEET E-503. PLEASE |
| | CORRECT AS APPLICABLE. NEC 215.5 |
| | 5) PLEASE CORRECT INCONSISTENT TRANSFORMER RATING AND |
| | OVERCURRENT PROTECTION BETWEEN PANELS 4P2 AND 2P2. FBC |
| | 107.2 |
| | 6) PLEASE CORRECT INCONSISTENT TRANSFORMER RATING AND |
| | OVERCURRENT PROTECTION BETWEEN PANELS 2F8A AND 4F8. FBC |
| | 107.2 |
| | 7) PLEASE CORRECT INCONSISTENT TRANSFORMER RATING AND |
| | OVERCURRENT PROTECTION BETWEEN PANELS 2Q9 AND 4Q9. FBC |
| | 107.2 |
| | 8) ESB SWITCHBOARD SCHEDULE DETAILS TWO FIRE PUMPS ON |
| | SHEET E-704, RISER DETAILS ONE FIRE PUMP CORRECT AS |
| | APPLICABLE. FBC 107.2 |
| | 9) PLEASE PROVIDE A LEGEND FOR SYMBOLS USED ON ONE LINE |
| | DIAGRAMS. SYMBOL FR AND G. FBC 107.2 |
| | 10) PLEASE PROVIDE DETAILS ON RISER DIAGRAMS SHOWING |
| | COMPLIANCE WITH NEC 215.10 AND 230.95 FOR 1000 AMP AND |
| | ABOVE EQUIPMENT GROUND FAULT PROTECTION. FBC 107.2 |
| | 11) PLEASE PROVIDE NOTES STATING ALL LOW VOLTAGE SYSTEM |
| | WIRING INCLUDING BUT NOT LIMITED TO, DATA, PHONE, |
| | ACCESS CONTROL, FIRE ALARM, BDA, REQUIRE SEPARATE |
| | PERMITS FOR EACH SYSTEM. ADDITIONALLY, GENERATORS, |
| | LIGHTNING PROTECTION, PV SYSTEMS, POOLS, SIGNS AND |
| | LANDSCAPE LIGHTING REQUIRE SEPARATE PERMITS. |
| | 12) ELECTRIC ROOMS ON 2ND AND 3RD FLOOR DETAILS |
| | EQUIPMENT WITH OVERCURRENT DEVICES RATED 800 AMPS OR |
| | MORE. IT APPEARS THE DOORS DETAILED AT THESE ROOMS ARE |
| | NOT EQUIPPED WITH PANIC DOOR HARDWARE. NEC 110.26 |
| | (3)(C) |
| | 13) RISER DIAGRAM ON SHEET E-504 DETAILS CONDUCTORS |
| | FROM DOF TO OFFICE ATS AS 400Y. SHEET E- 503 DETAILS |
| | 3000 Y CONDUCTORS. PLEASE CORRECT AS APPLICABLE. NEC |
| | 215.5 |
| | 14) RISER DIAGRAM ON SHEET 503 DETAILS 400 Y CONDUCTORS |
| | FROM OFFICE ATS TO ESB SWITCHBOARD FED FROM 3000 AMP |
| | BREAKER. PLEASE CORRECT AS APPLICABLE. NEC 215.5 |
| | 15) RISER DIAGRAM ON SHEET E-503 DETAILS 400 Y |
| | CONDUCTORS FROM ATS OFFICE TO MAIN 1. SHEET E-501 |
| | DETAILS 3000 Y CONDUCTORS FROM MAIN 1 TO ATS OFFICE. |
| | PLEASE CORRECT AS APPLICABLE. NEC 215.5 |
| | 16) PLEASE DETAIL DESTINATION OF LOAD SIDE CONDUCTORS |
| | FROM ALL ATS EQUIPMENT ON SHEET E-503. NEC 215.5 |
| | 17) PLEASE ENSURE TO CORRECT ANY PANEL SCHEDULES |
| | MISLABELED FROM THE ABOVE CORRECTIONS. NEC 215.5 |
| | 18) PLEASE PROVIDE DETAILS ON VERTICAL CONDUCTOR |
| | SUPPORTS. ALL APPLICABLE CONDUCTORS, IE, GENERATOR, |
| | ETC. NEC 300.19 |
| | 19) FEED BREAKER FOR PANEL 4P1, ON PANEL SCHEDULE FOR |
| | DPP, ON SHEET E-703, IS DETAILED AS 20 AMP. PANEL |
| | SCHEDULE 4P1 ON SHEET E 701 IS DETAILED AS A 400 AMP |
| | MAIN BREAKER PANEL. PLEASE CORRECT AS APPLICABLE. NEC |
| | 215.5 |
| | 20) PLEASE PROVIDE ALL RATINGS FOR SWITCHBOARDS DMP, |
| | DQP ON SHEET E-703. NEC 215.5 |
| | 21) PANEL SCHEDULES DETAIL PANEL 4E2 WITH 400 AMP MAIN |
| | BREAKER FED FROM A 150 AMP BREAKER FROM PANEL DLS. IF |
| | THIS IS INCORRECT, PLEASE CORRECT AS APPLICABLE. NEC |
| | 215.5 |
| | 22) FEED BREAKER FOR PANEL 4P4, ON PANEL SCHEDULE FOR |
| | DPP, ON SHEET E-703, IS DETAILED AS 20 AMP. PANEL |
| | SCHEDULE 4P4 ON SHEET E 701 IS DETAILED AS A 250-AMP |
| | BUS RATING WITH A 400 AMP MAIN BREAKER. PLEASE CORRECT |
| | AS APPLICABLE. NEC 215.5 |
| | 23) RISER SHEET E-504 DETAILS PANEL 4P7 BEING FED FROM |
| | PANELBOARD DPP. PANEL 4P7 IS NOT DETAILED IN PANEL |
| | SCHEDULE ON FOR DPP, SHEET E-703. PLEASE CORRECT AS |
| | APPLICABLE. NEC 215.5 |
| | 24) PLEASE PROVIDE DETAILS ON MINI POWER CENTERS. NEC |
| | 215.5 |
| | 25) DOF SWITCHBOARD SCHEDULE ON SHEET E 705 DETAIL 3000 |
| | AMP BUSWAY FEED. RISER DIAGRAM ON SHEET E 504, DETAILS |
| | A 2000 AMP BUSWAY FEED. PLEASE CORRECT AS APPLICABLE. |
| | NEC 215.5 |
| | 26) PANEL SCHEDULES ON SHEET E-709 DETAIL PANELS BEING |
| | FED FROM 3000 AMP BUSWAY. RISER DIAGRAM ON SHEET E-504 |
| | DETAILS A 2000 AMP BUSWAY FEEDING THESE PANELS. PLEASE |
| | CORRECT AS APPLICABLE. NEC 215.5 |
| | 27) PANEL SCHEDULES ON SHEET E-710 DETAIL PANELS BEING |
| | FED FROM 3000 AMP BUSWAY. RISER DIAGRAM ON SHEET E-504 |
| | DETAILS A 2000 AMP BUSWAY FEEDING THESE PANELS. PLEASE |
| | CORRECT AS APPLICABLE. NEC 215.5 |
| | 28) TRANSFORMER ON PANEL SCHEDULE 2M19, SHEET E-711, |
| | INCORRECTLY DETAILED AS A T6. PLEASE CORRECT AS |
| | APPLICABLE. NEC 215.5 |
| | 29) TRANSFORMER ON PANEL SCHEDULE 2F20A, SHEET E-712, |
| | INCORRECTLY DETAILED AS A T6. PLEASE CORRECT AS |
| | APPLICABLE. NEC 215.5 |
| | 30) TRANSFORMER ON PANEL SCHEDULE 2F21A, SHEET E-712, |
| | INCORRECTLY DETAILED AS A T6. PLEASE CORRECT AS |
| | APPLICABLE. NEC 215.5 |
| | 31) PANEL SCHEDULE DETAILS PANEL 2F21A, SHEET E-712, AS |
| | 250 BUS AMP RATING WITH A 400 AMP MAIN BREAKER. IF THIS |
| | IS INCORRECT, PLEASE CORRECT AS APPLICABLE. NEC 215.5 |
| | 32) TRANSFORMER ON PANEL SCHEDULE 2F22A, SHEET E-713, |
| | INCORRECTLY DETAILED AS A T6. PLEASE CORRECT AS |
| | APPLICABLE. NEC 215.5 |
| | 33) TRANSFORMER ON PANEL SCHEDULE 2M22, SHEET E-713, |
| | INCORRECTLY DETAILED AS A T6. PLEASE CORRECT AS |
| | APPLICABLE. NEC 215.5 |
| | 34) TRANSFORMER ON PANEL SCHEDULE 2F23A, SHEET E-713, |
| | INCORRECTLY DETAILED AS A T6. PLEASE CORRECT AS |
| | APPLICABLE. NEC 215.5 |
| | 35) PANEL SCHEDULE DETAILS PANEL 2F23A, SHEET E-712, AS |
| | 250 BUS AMP RATING WITH A 400 AMP MAIN BREAKER. IF THIS |
| | IS INCORRECT, PLEASE CORRECT AS APPLICABLE. NEC 215.5 |
| | 36) TRANSFORMER ON PANEL SCHEDULE 4E23, SHEET E-713, |
| | INCORRECTLY DETAILED AS A T5. PLEASE CORRECT AS |
| | APPLICABLE. NEC 215.5 |
| | 37) TRANSFORMER ON PANEL SCHEDULE 2F24A, SHEET E-714, |
| | INCORRECTLY DETAILED AS A T6. PLEASE CORRECT AS |
| | APPLICABLE. NEC 215.5 |
| | 38) PANEL SCHEDULE 4F24 DETAILS PANEL AS MLO FED FROM |
| | 1000 AMP BUSWAY. IF THIS IS INCORRECT, PLEASE CORRECT |
| | AS APPLICABLE. NEC 215.5 |
| | 39) TRANSFORMER ON PANEL SCHEDULE 4Q24, SHEET E-714, |
| | DETAILS A T5. RISER DIAGRAM ON SHEET E 505 DETAILS A T4 |
| | TRANSFORMER. PLEASE CORRECT AS APPLICABLE. NEC 215.5 |
| | 40) TRANSFORMER ON PANEL SCHEDULE 2Q24, SHEET E-714, |
| | INCORRECTLY DETAILED AS A T6. PLEASE CORRECT AS |
| | APPLICABLE. NEC 215.5 |
| | 41) PANEL SCHEDULE DETAILS PANEL 2Q24, SHEET E-714, AS |
| | 400 BUS AMP RATING WITH A 400 AMP MAIN BREAKER. IF THIS |
| | IS INCORRECT, PLEASE CORRECT AS APPLICABLE. NEC 215.5 |
| | 42) PANEL SCHEDULE DETAILS PANEL 2MR, SHEET E-714, AS |
| | 400 BUS AMP RATING WITH A 400 AMP MAIN BREAKER. IF THIS |
| | IS INCORRECT, PLEASE CORRECT AS APPLICABLE. NEC 215.5 |
| | 43) PANEL SCHEDULE DETAILS PANEL 2QR, SHEET E-714, AS |
| | 400 BUS AMP RATING WITH A 400 AMP MAIN BREAKER. IF THIS |
| | IS INCORRECT, PLEASE CORRECT AS APPLICABLE. NEC 215.5 |
| | 44) PLEASE ENSURE ALL RISERS AND PANEL SCHEDULES |
| | CONCUR. NEC 215.5 |
| | |