| Plan Review Notes For Permit 21080887 |
| Permit Number |
21080887 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-09-15 16:06:53 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE GENERATOR EXHAUST IS REQUIRED TO BE AT LEAST 10 | | | FEET FROM ANY OPENINGS INTO A BUILDING. PLEASE NOTE | | | THIS ON THE SURVEY. | | | | | | R303.5.1 INTAKE OPENINGS | | | | | | MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE OPENINGS | | | SHALL BE LOCATED NOT LESS THAN 10 FEET (3048 MM) FROM | | | ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS VENTS, | | | CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS, PARKING LOTS | | | AND LOADING DOCKS. | | | | | | FOR THE PURPOSE OF THIS SECTION, THE EXHAUST FROM | | | DWELLING UNIT TOILET ROOMS, BATHROOMS AND KITCHENS | | | SHALL NOT BE CONSIDERED AS HAZARDOUS OR NOXIOUS. | | | | | | |
|