| Date |
Text |
| 2021-08-24 16:21:48 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1 |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | NFPA 54 = NATIONAL FUEL GAS CODE |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 21080885 7310 GEORGIA AVE # 1 |
| | MASTER PERMIT 19120571 |
| | |
| | 1ST REVIEW |
| | |
| | GAS COMMENTS: DENIED |
| | |
| | 1.PER WPB FBC 107.2.1, PROVIDE GAS FLOOR PLAN SHOWING |
| | LOCATION OF RELOCATED METER/REGULATOR. |
| | |
| | 2. FBC FG TABLE 402.4(21) IS NOT THE CORRECT TABLE FOR |
| | THE SIZING OF THE 2PSI POLYETHYLENE PIPING FROM METER |
| | TO BUILDING. PER WPB FBC 107.2.1, PROVIDE CORRECT TABLE |
| | (SEE TABLE 402.4(22). |
| | |
| | 3.A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY |
| | AHEAD OF THE MP REGULATOR AT THE ENTRY POINT TO THE |
| | BUILDING PER FBC FG 409.4. |
| | |
| | 4.THE DEVICE AT THE LOCATION OF THE EMERGENCY SHUTOFF |
| | VALVE IS LABELED PRV. AN EMERGENCY SHUT OFF VALVE IS |
| | NOT INDICATED. PER WPB FBC 107.2.1, CLARIFY AND |
| | IDENTIFY THE EMERGENCY SHUTOFF VALVE. |
| | |
| | 5. IT IS NOTED THAT THE DEVELOPED LENGTH OF THE PIPING |
| | IS 91 FEET. THE PIPING APPEARS TO BE SIZED BASED ON |
| | EACH SYSTEM BEING A MAXIMUM OF 100 FEET WHEN APPLYING |
| | THE CORRECT TABLES. PER WPB FBC 107.2.1, CONFIRM THAT |
| | EACH SYSTEM, 2LB. AND LESS THAN 2LB. DOES NOT EXCEED |
| | 100? TOTAL LENGTH OR PROVIDE THE ACTUAL MAXIMUM LENGTH |
| | FOR EACH SYSTEM. |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | MOBILE 561-246-0882 |
| | PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND |
| | THURSDAYS |
| | |