2021-09-27 09:33:3109/27/21 1ST POOL PLUMBING REVIEW**DENIED** WITH
 COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON SHEET A3.0.2, IN DETAIL ONE, THE ELEVATION FOR
 THE SINK OF 34 INCHES TO THE TOP OF THE COUNTER IS
 MISSING. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 2. ON SHEET A3.0.3;
  
 A. ON DETAIL ONE, FOUR, AND SEVEN, THE TOILET GRAB BAR
 SAYS 6 INCHES FROM THE WALL, WHICH IS NOT AN ACTUAL
 NUMBER AS THE TOILET IS 16 INCHES TO 18 INCHES TO THE
 CENTER, AND THAT NUMBER MAY CONFUSE THE INSTALLER.
 WOULD YOU PLEASE CORRECT PER THE 2020 FBC ACC SEC.
 604.2 LOCATION AND WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 B. ON DETAIL ONE, FOUR, FIVE, SEVEN, AND TEN, ON THE
 MIRROR, WOULD YOU PLEASE ADD THAT THE 40? TO THE
 REFLECTIVE SIDE PER THE 2020 FBC ACC SEC. 603.3.
  
 C. WOULD YOU PLEASE SHOW THE HEIGHT FOR ALL PARTITIONS
 BETWEEN THE URINAL AND TOILET PER THE 2020 FBC SEC. P
 405.3.5.
  
 D. ON DETAIL THREE AND FIVE, WOULD YOU PLEASE SHOW THAT
 THE 27 INCHES UNDER CABINET IN FILED A306 REFERENCE IS
 NOT CLEAR TO THE INSTALLER. WOULD YOU PLEASE PROVIDE
 PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 E. ON DETAIL EIGHT, WOULD YOU PLEASE SHOW THE TOILET
 SEATS NEED TO BE 17 INCHES TO 19 INCHES MAXIMUM
 MEASURED TO THE TOP OF THE SEAT PER THE 2020 FBC ACC
 SEC. 604.4 SEATS. ON THAT SAME DETAIL, THE SHOWER GRAB
 BARS FROM THE WALL AND LENGTH ARE NOT GIVEN. WOULD YOU
 PLEASE PROVIDE PER THE 2020 FBC SEC. ACC 608.3.2
 STANDARD ROLL-IN TYPE SHOWER COMPARTMENTS.
  
 F. ON DETAIL A, THE TOILET GRAB BAR SAYS 6 INCHES FROM
 THE WALL, WHICH IS NOT AN ACTUAL NUMBER AS THE TOILET
 IS 16 INCHES TO 18 INCHES TO THE CENTER, WHICH MAY
 CONFUSE THE INSTALLER. WOULD YOU PLEASE SHOW THE 16
 INCHES TO 18 INCHES CORRECT PER THE 2020 FBC ACC SEC.
 604.2 LOCATION AND WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 G. ON DETAIL 14, WOULD YOU PLEASE SHOW THE 27 INCHES
 UNDER THE LOW SIDE OF THE DRINKING FOUNTAIN KNEE
 CLEARANCE AND SHOW A DETAIL OF THE CLEAR FLOOR SPACE
 PER THE 2020 FBC SEC. 306.3.
  
 H. ON DETAIL A, THE URINAL DOES NOT HAVE THE CLEAR
 FLOOR SPACE AND THE 15 INCHES FROM OTHER FIXTURES.
 WOULD YOU PLEASE CORRECT PER THE WPB AMENDMENTS TO THE
 FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 I. WOULD YOU PLEASE PROVIDE DETAIL FOR SUPPORT OF GRAB
 BAR AND A REFERENCE IF USING A DIFFERENT PAGE PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 3. ON SHEET P1.1, THE SERVICE SINK (MOP SINK)
 SURROUNDING THE WALL SHALL BE A NON-ABSORBENT SURFACE
 IN ACCORDANCE WITH THE 2020 FBC BUILDING SEC. 1210.2.2
 AND 2020 FBC SEC. P 310.3. WOULD YOU PLEASE MAKE A NOTE
 ON THIS SHEET?
  
 4. ON SHEET P2.1; GREAT JOB ON THE RECIRCULATING OF THE
 HOT WATER SYSTEM. THIS IS THE FIRST TIME SOME GOT IT
 RIGHT.
  
 A. ON NOTE FIVE FOR THE COFFEE MAKER/ICE MAKER REQUIRES
 AN INLINE VACUUM BREAKER THAT COMPLIES WITH THE ASSE
 1024 NON-CARBONATED PER THE 2020 FBC SEC. 608.17.1.2
  
 B. ON DETAIL TWO FOR THE SHUT-OFF VALVES, THEY HAVE
 ACCESS PANELS SHOWN. PLEASE ADD ACES PANELS SIZE PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 C. THE DISHWASHER SHOWS HOT WATER TO IT IS THE UNIT A
 HOT OR COLD WATER INTAKE. WOULD YOU PLEASE CLARIFY PER
 THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS?
  
 5. ON SHEET P3.2; GREAT JOB ON THE RECIRCULATING OF THE
 HOT WATER SYSTEM. THIS IS THE FIRST TIME SOME GOT IT
 RIGHT.
  
 A. ON THE DRINKING FOUNTAIN, IT HAS A QUICK CLOSING
 VALVE WOULD. WOULD YOU PLEASE SHOW A SHUT-OFF VALVE ON
 TOP AND A HAMMER ARRESTOR? WOULD YOU PLEASE SHOW THIS
 ON DISHWASHER AND ICE MAKERS AS WELL PER THE 2020 FBC
 SEC. P604.9, P416.5, P607.1.2, & P608.3.
  
 B. ON THE WATER HEATER, SHOW THE MIXING VALVE OR CIRCLE
 WITH A NOTE TO THE DETAIL ON PAGE P4.1 PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 6. ON SHEET P-4;
  
 A. LAVATORY WATER SUPPLY AND DRAINPIPES UNDER SIDE
 SHALL BE INSULATED OR OTHERWISE CONFIGURED TO PROTECT
 AGAINST CONTACT PER THE 2020 FBC ACC SEC. 606.5
  
 B. PLEASE PROVIDE THE LOCATION OF THE WATER CLOSET
 FLUSH CONTROL PER THE 2020 FBC SEC. 604.6 FLUSH
 CONTROLS.
  
 C. SEATS OF WATER CLOSETS SHALL BE OPEN-FRONT TYPE PER
 2020 FBC P 425.3 WATER CLOSET SEATS.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  