| 2021-09-01 16:26:47 | THE CONFERENCE ROOMS OUTDOOR AIR CALCULATIONS CAME UP | | | SHORT. BASED ON FBC M 403.3.1.1 AND TABLE 403.3.1.1 THE | | | MINIMUM REQUIRED OUTDOOR AIR FOR THIS SQUARE FOOTAGE IS | | | 302 CFM. THIS WOULD ALSO MAKE THE TOTAL CFM'S FOR THE | | | SPACE TO BE 721 INSTEAD OF 715 CFM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | | | | | | | |
|