| Plan Review Notes For Permit 21080880 |
| Permit Number |
21080880 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2021-08-31 08:02:46 | ROOFING | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) ROOFING SYSTEM TO BE USED ON THE PROVIDED PRODUCT | | | APPROVAL (TPO 18-0523.05) REQUIRES ADDITIONAL SIGNED | | | AND SEALED ATTACHMENT DETAILS FROM AN ARCHITECT OR | | | ENGINEER FOR ROOF WIND ZONES 3 WHICH REQUIRE A HIGHER | | | PRESSURE THAN THE MAXIMUM SHOWN ON THE PRODUCT APPROVAL | | | (-60) - SEE GENERAL LIMITATION NUMBER 7 ON THE PRODUCT | | | APPROVAL. DRAWING S101 FROM PERMIT NUMBER 20120907 | | | SHOWS ZONE 3 WIND PRESSURE OF (-72) | | | 2) PLEASE PROVIDE THE FRONT PAGES OF THE PRODUCT | | | APPROVAL FOR THE (TPO 18-0523.05). | | | 3) PLEASE PROVIDE THE FRONT PAGES FOR THE PRODUCT | | | APPROVAL FOR THE SHINGLES (FL10124) |
|