| 2021-11-18 11:35:36 | 3RD REVIEW FBC-2020 PLUMBING |
| | PERMIT- 21080875 |
| | 11/18/21 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE |
| | 1ST AND 2ND REVIEWS ARE LISTED BELOW WITH ADDITIONAL |
| | NOTES IN CAP LETTERS FOR FURTHER CLARIFICATION. |
| | |
| | 4) FAILED-A5.1: MISSING ACCESSIBILITY DETAILS FOR THE |
| | COMMUNITY FLOOR PER FBC ACC: SEE COMMENTS A, B, C. |
| | A) FAILED. CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS |
| | FOR THE WATER CLOSETS- SECTION 604.3. DIMENSIONS NOT |
| | PROVIDED |
| | B) FAILED. CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS |
| | FOR THE LAVATORIES- SECTION 606.2. DIMENSIONS NOT |
| | PROVIDED. |
| | C) FAILED. TURNING SPACE DIAMETERS- SECTION 304.3. |
| | DIMENSIONS NOT PROVIDED. |
| | |
| | 9) FAILED. P3.1: CLEANOUTS MISSING AT THE JUNCTIONS OF |
| | THE KITCHEN AND BATH BUILDING DRAIN/SEWER LINE |
| | JUNCTION- SECTION 708.1.3 FBC P. |
| | |
| | 10) FAILED. P3.1: ONE OF THE EWC DRAINS IS MISSING FROM |
| | THE DRAWING- SECTION 107.2.1 WPB. |
| | |
| | 11) FAILED. P3.1: PROVIDE VENTING FOR THE EWC, MOP |
| | SINK, AND HUB DRAIN- SECTION 901.2.1 FBC P. |
| | |
| | 13) FAILED. P0.1 & P3.2: REFER TO THE LEGEND AND |
| | PROVIDE THE CORRECT LINE SYMBOLS FOR THE CW, HW, & HWR |
| | LINES ON THE FLOOR PLAN DRAWING AND THE RISER- SECTION |
| | 107.2.1 WPB. PLEASE SEE COMMENT #4 AND CORRECT THE HWR |
| | CONNECTION LOCATION. PLEASE CLARIFY IF THERE IS A HW |
| | LINE RUNNING TO LAV-3- SECTION 107.2.1 WPB. HWR LINE TO |
| | THE FIXTURES NOT SHOWN ON THE ISO OR THE FLOOR PLAN. |
| | |
| | NEW COMMENTS |
| | 1) PLEASE AT A NOTE ON P3.2 OR P0.1 TO INDICATE MIXING |
| | VALVES CONFORM TO ASSE 1070- SECTION 607.2.1 FBC P. |
| | |
| | 2) P0.1: PROVIDE A NOTE TO INDICATE WHICH FIXTURES AND |
| | DEVICES WILL BE DEFERRED SUBMITTALS- SECTION 107.3.4 |
| | WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |