Plan Review Notes
Plan Review Notes For Permit 21080875
Permit Number 21080875
Review Stop P
Sequence Number 3
Notes
Date Text
2021-11-18 11:35:363RD REVIEW FBC-2020 PLUMBING
 PERMIT- 21080875
 11/18/21
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE
 1ST AND 2ND REVIEWS ARE LISTED BELOW WITH ADDITIONAL
 NOTES IN CAP LETTERS FOR FURTHER CLARIFICATION.
  
 4) FAILED-A5.1: MISSING ACCESSIBILITY DETAILS FOR THE
 COMMUNITY FLOOR PER FBC ACC: SEE COMMENTS A, B, C.
 A) FAILED. CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS
 FOR THE WATER CLOSETS- SECTION 604.3. DIMENSIONS NOT
 PROVIDED
 B) FAILED. CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS
 FOR THE LAVATORIES- SECTION 606.2. DIMENSIONS NOT
 PROVIDED.
 C) FAILED. TURNING SPACE DIAMETERS- SECTION 304.3.
 DIMENSIONS NOT PROVIDED.
  
 9) FAILED. P3.1: CLEANOUTS MISSING AT THE JUNCTIONS OF
 THE KITCHEN AND BATH BUILDING DRAIN/SEWER LINE
 JUNCTION- SECTION 708.1.3 FBC P.
  
 10) FAILED. P3.1: ONE OF THE EWC DRAINS IS MISSING FROM
 THE DRAWING- SECTION 107.2.1 WPB.
  
 11) FAILED. P3.1: PROVIDE VENTING FOR THE EWC, MOP
 SINK, AND HUB DRAIN- SECTION 901.2.1 FBC P.
  
 13) FAILED. P0.1 & P3.2: REFER TO THE LEGEND AND
 PROVIDE THE CORRECT LINE SYMBOLS FOR THE CW, HW, & HWR
 LINES ON THE FLOOR PLAN DRAWING AND THE RISER- SECTION
 107.2.1 WPB. PLEASE SEE COMMENT #4 AND CORRECT THE HWR
 CONNECTION LOCATION. PLEASE CLARIFY IF THERE IS A HW
 LINE RUNNING TO LAV-3- SECTION 107.2.1 WPB. HWR LINE TO
 THE FIXTURES NOT SHOWN ON THE ISO OR THE FLOOR PLAN.
  
 NEW COMMENTS
 1) PLEASE AT A NOTE ON P3.2 OR P0.1 TO INDICATE MIXING
 VALVES CONFORM TO ASSE 1070- SECTION 607.2.1 FBC P.
  
 2) P0.1: PROVIDE A NOTE TO INDICATE WHICH FIXTURES AND
 DEVICES WILL BE DEFERRED SUBMITTALS- SECTION 107.3.4
 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  