Plan Review Notes
Plan Review Notes For Permit 21080875
Permit Number 21080875
Review Stop M
Sequence Number 3
Notes
Date Text
2022-01-19 11:27:441ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21080875
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE THE GLOBAL PLASMA SOLUTIONS FOR THIS
 BUILDING BASED ON THE CORRECT USE OF SPACE. UNDER THE
 OUTSIDE AIR CALCULATIONS LISTED ON PAGE 1 OF 7 THE
 COMMUNITY CENTER IS CLASSIFIED UNDER THE OCCUPANCY
 CLASSIFICATION AS BOTH MULTIUSE ASSEMBLY AND
 LOBBIES/PRE-FUNCTION. THE USE OF SPACE FOR THIS AREA
 SHOULD BE CLASSIFIED AS MULTIUSE ASSEMBLY. THE
 CALCULATION BASED ON FBC M TABLE 403.3.1.1 IS
 UNDERSIZED. THIS IN TURN MEANS THE GLOBAL PLASMA
 SOLUTIONS CALCULATIONS IS ALSO VERY LOW. ACCORDING TO
 FBC M 403.3.1.1 AND TABLE 403.3.1.1 THE CALCULATION FOR
 THIS SPACE IS AS FOLLOWS: 1780 SQ FT / 1000 = 1.78;
 1.78 X 100 OCCUPANT DENSITY = 178 OCCUPANTS; 178 X 7.5
 =1335; 1780 SQ. FT. X .06 = 106.8; 1335 + 106.8 =
 1441.8 CFM OF OUTSIDE AIR REQUIRED FOR THE MULTIUSE
 ASSEMBLY SPACE.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728