Plan Review Notes
Plan Review Notes For Permit 21080875
Permit Number 21080875
Review Stop P
Sequence Number 2
Notes
Date Text
2021-11-10 11:15:052ND REVIEW FBC-2020 PLUMBING
 PERMIT- 21080875
 11/10/21
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE
 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTES IN
 CAP LETTERS FOR FURTHER CLARIFICATION.
  
 1) FAILED- CODE DATA: PROVIDE ON THE PLAN A LIST OF
 CURRENT FLORIDA CODES AND STANDARDS USED IN THE DESIGN
 OF THE PROJECT. PLEASE NOTE THAT ALTERATIONS TO THE
 PUBLIC AND PRIVATE BATHROOM FACILITIES SHALL BE IN
 COMPLIANCE WITH THE FBC-2020 7TH EDITION ACCESSIBILITY
 CODE, AND THE FAIR HOUSING ACT DESIGN MANUAL. THE
 CURRENT PLANS PROVIDE NO INFORMATION OR GUIDANCE AS TO
 WHICH CODES SHOULD BE APPLIED WHERE. ALSO MISSING ARE
 ENLARGED, DIMENSIONED FLOOR PLAN DRAWINGS AND
 ARCHITECTURAL DETAILS FOR PLUMBING FIXTURE
 INSTALLATIONS IN THE COMMUNITY BATHROOMS AND COMMUNITY
 KITCHEN- SECTION 107.2.1 WPB. NUMEROUS TARGETS CALL OUT
 SHEET A7.2 WHICH IS NOT INCLUDED WITH THE PLAN SET.
 SHEET LS0.5: FBC-2020 BUILDING CODES INCLUDING PLUMBING
 AND ACCESSIBILITY HAVE NOT BEEN NOTED ON THE PLAN.
  
 3) FAILED: PROVIDE PLUMBING FIXTURE CALCULATIONS IN
 COMPLIANCE WITH TABLE 403.1 FBC P. PROVIDE ON A
 SCHEDULE THAT INDICATES THE REQUIRED AND PROVIDED
 FIXTURES FOR THE COMMUNITY OCCUPANCY. SHEET LS0.5: THE
 REVISED PLAN INDICATES A MIXED OCCUPANCY OF BUSINESS
 AND ASSEMBLY. BASED ON TABLE 403.1 AND 403.1.1 (3)
 WATER CLOSETS ARE REQUIRED FOR FEMALE USE HOWEVER THE
 PLANS INDICATE TWO. THERE IS A 3RD TOILET ROOM THAT IS
 NOT LABELED AS EITHER MEN?S OR WOMEN?S. IF THIS IS THE
 LOCATION OF THE REQUIRED FEMALE WATER CLOSET, IT MUST
 BE LABELED AS SUCH- SECTION 403.2 FBC P. A) PLEASE
 REVISE THE PLUMBING FIXTURE REQUIREMENTS NOTES AND
 CALCULATIONS TO BE IN CPOMPLIANCE WITH THE CODE.
 FIXTURE CALCULATIONS SHALL BE DONE ACCORDING TO TABLE
 403.1 AND OCCUPANT PERCENTAGES.
  
 4) FAILED-A5.1: MISSING ACCESSIBILITY DETAILS FOR THE
 COMMUNITY FLOOR PER FBC ACC: SEE COMMENTS A, B, C, M, &
 O.
 A) FAILED. CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS
 FOR THE WATER CLOSETS- SECTION 604.3. NOT PROVIDED
 B) FAILED. CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS
 FOR THE LAVATORIES- SECTION 606.2. NOT PROVIDED.
 C) FAILED. TURNING SPACE DIAMETERS- SECTION 304.3. NOT
 PROVIDED.
 M) FAILED. CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR
 THE KITCHEN SINK- SECTION 606.2. NOT PROVIDED.
 O) FAILED. DRINKING FOUNTAINS: REFER TO SECTIONS 306,
 307, AND 602 FBC ACC AND PROVIDE DRINKING FOUNTAIN
 INSTALLATION DETAILS AND ELEVATION VIEWS SHOWING KNEE
 AND TOE CLEARANCES, SPOUT HEIGHTS, AND SPOUT LOCATIONS.
 SHOW THE REQUIRED 30 X 48 IN. CLEAR FLOOR SPACE FOR A
 FORWARD WHEELCHAIR APPROACH TO THE FOUNTAIN- SECTION
 602.2 FBC ACC. PLEASE INDICATE HOW THE LOCATIONS OF THE
 FOUNTAINS WILL BE IN COMPLIANCE WITH SECTION 307.2
 PROTRUSION LIMITS. PROTRUSION IMIT COMPLIANCE NOT
 PROVIDED.
  
 9) FAILED. P3.1: CLEANOUTS MISSING AT THE JUNCTIONS OF
 THE KITCHEN AND BATH BUILDING DRAIN/SEWER LINE
 JUNCTION- SECTION 708.1.3 FBC P. THE REVISED PLAN SHEET
 WAS NOT UPLOADED.
  
 10) FAILED. P3.1: ONE OF THE EWC DRAINS IS MISSING FROM
 THE DRAWING- SECTION 107.2.1 WPB. THE REVISED PLAN
 SHEET WAS NOT UPLOADED.
  
 11) FAILED. P3.1: PROVIDE VENTING FOR THE EWC, MOP
 SINK, AND HUB DRAIN- SECTION 901.2.1 FBC P. THE REVISED
 PLAN SHEET WAS NOT UPLOADED.
  
 13) FAILED. P0.1 & P3.2: REFER TO THE LEGEND AND
 PROVIDE THE CORRECT LINE SYMBOLS FOR THE CW, HW, & HWR
 LINES ON THE FLOOR PLAN DRAWING AND THE RISER- SECTION
 107.2.1 WPB. PLEASE SEE COMMENT #4 AND CORRECT THE HWR
 CONNECTION LOCATION. PLEASE CLARIFY IF THERE IS A HW
 LINE RUNNING TO LAV-3- SECTION 107.2.1 WPB. HWR LINE TO
 THE FIXTURES NOT SHOWN ON THE ISO OR THE FLOOR PLAN.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER