| 2021-11-17 10:27:55 | 2ND REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21080875 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) IF USING THE ASHRAE 62.1-2013 TO DESIGN THESE |
| | SYSTEMS YOU MUST SUBMIT THE ENTIRE DOCUMENTS, PLEASE |
| | PROVIDE ALL OF THE CALCULATIONS FROM ASHRAE 62.1- 2013 |
| | INCLUDING THE TIME AVERAGE ANALYSIS. FBC M 312.1 |
| | |
| | 2) PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS FOR EACH |
| | USE OF SPACE BASED ON THE OCCUPANCY CATEGORY NAMING OF |
| | ASHRAE TABLE 6.2.2.1. EXAMPLE: COMMUNITY CENTER IS NOT |
| | ONE OF THE OCCUPANCY CATEGORIES IN THE TABLE. THIS AREA |
| | WOULD TEND TO BE CALCULATED AS A MULTIUSE ASSEMBLY. |
| | ASHRAE 62.1-2013 |
| | |
| | 3) SHEET M3.1: PLEASE PROVIDE APPLIANCE ANCHORAGE |
| | DETAILS FOR HPU-4 AND HPU-5. FBC M 301.15 |
| | |
| | 4) PLEASE PROVIDE THE INFORMATION FOR THE BATH EXHAUST |
| | FANS. FBC 107.2.1 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |