2021-09-21 13:14:031ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21080875
 9/20/21
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) CODE DATA: PROVIDE ON THE PLAN A LIST OF CURRENT
 FLORIDA CODES AND STANDARDS USED IN THE DESIGN OF THE
 PROJECT. PLEASE NOTE THAT ALTERATIONS TO THE PUBLIC AND
 PRIVATE BATHROOM FACILITIES SHALL BE IN COMPLIANCE WITH
 THE FBC-2020 7TH EDITION ACCESSIBILITY CODE, AND THE
 FAIR HOUSING ACT DESIGN MANUAL. THE CURRENT PLANS
 PROVIDE NO INFORMATION OR GUIDANCE AS TO WHICH CODES
 SHOULD BE APPLIED WHERE. ALSO MISSING ARE ENLARGED,
 DIMENSIONED FLOOR PLAN DRAWINGS AND ARCHITECTURAL
 DETAILS FOR PLUMBING FIXTURE INSTALLATIONS IN THE
 COMMUNITY BATHROOMS AND COMMUNITY KITCHEN- SECTION
 107.2.1 WPB. NUMEROUS TARGETS CALL OUT SHEET A7.2 WHICH
 IS NOT INCLUDED WITH THE PLAN SET.
  
 2) PROVIDE A PLAN INDEX- SECTION 107.2.1 WPB.
  
 3) PROVIDE PLUMBING FIXTURE CALCULATIONS IN COMPLIANCE
 WITH TABLE 403.1 FBC P. PROVIDE ON A SCHEDULE THAT
 INDICATES THE REQUIRED AND PROVIDED FIXTURES FOR THE
 COMMUNITY OCCUPANCY.
  
 4) A5.1: MISSING ACCESSIBILITY DETAILS FOR THE
 COMMUNITY FLOOR PER FBC ACC:
 A) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE
 WATER CLOSETS- SECTION 604.3.
 B) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE
 LAVATORIES- SECTION 606.2.
 C) TURNING SPACE DIAMETERS- SECTION 304.3.
 D) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE
 WALLS- SECTION 604.2.
 E) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOORS- SECTION 604.4.
 F) HEIGHTS OF THE LAVATORY SINK RIMS OR COUNTER
 SURFACES FROM THE FINISHED FLOORS- SECTION 606.3.
  
 G) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO
 THE REFLECTIVE SURFACES- SECTION 603.3
 H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4,
 FIGURES 604.5.1 & 604.5.2.
 I) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS -
 SECTION 604.6.
 J) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED
 FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND
 FIGURE 604.7.
 K) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION
 606.2.
 L) URINAL RIM HEIGHT AND CLEAR FLOOR SPACE DIAGRAM AND
 DIMENSION- SECTION 605.2 & 605.3.
 M) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 KITCHEN SINK- SECTION 606.2.
 N) HEIGHT OF THE KITCHEN SINK RIM OR COUNTER SURFACE
 FROM THE FINISHED FLOOR- SECTION 606.3.
 O) DRINKING FOUNTAINS: REFER TO SECTIONS 306, 307, AND
 602 FBC ACC AND PROVIDE DRINKING FOUNTAIN INSTALLATION
 DETAILS AND ELEVATION VIEWS SHOWING KNEE AND TOE
 CLEARANCES, SPOUT HEIGHTS, AND SPOUT LOCATIONS. SHOW
 THE REQUIRED 30 X 48 IN. CLEAR FLOOR SPACE FOR A
 FORWARD WHEELCHAIR APPROACH TO THE FOUNTAIN- SECTION
 602.2 FBC ACC. PLEASE INDICATE HOW THE LOCATIONS OF THE
 FOUNTAINS WILL BE IN COMPLIANCE WITH SECTION 307.2
 PROTRUSION LIMITS.
  
 5) P0.2: THE COMMUNITY WATER HEATER RECIRCULATION LINE
 SHALL CONNECT TO THE COLD WATER INLET LINE TO THE WATER
 HEATER. PLEASE CORRECT THE DRAWING SHOWING CONNECTION
 DIRECTLY TO THE WATER HEATER- SECTION 607.2.1 FBC P,
 AND R403.5.1.1 FBC EC.
  
 6) P0.2: REVISE THE COMMUNITY WATER HEATER DETAIL TO
 SHOW A PAN AND A PAN DRAIN LINE TO THE HUB DRAIN-
 SECTIONS 504.7- 504.7.2 FBC P.
  
 7) P0.1 & P0.2: PROVIDE HW PIPE INSULATION
 SPECIFICATIONS- TABLE C403.2.10 FBC EC.
  
 8) P0.2: SHOW REQUIRED HEAT TRAPS FOR THE COMMUNITY
 WATER HEATER- SECTION R403.5.5 FBC EC.
  
 9) P3.1: CLEANOUTS MISSING AT THE JUNCTIONS OF THE
 KITCHEN AND BATH BUILDING DRAIN/SEWER LINE JUNCTION-
 SECTION 708.1.3 FBC P.
  
 10) P3.1: ONE OF THE EWC DRAINS IS MISSING FROM THE
 DRAWING- SECTION 107.2.1 WPB.
  
 11) P3.1: PROVIDE VENTING FOR THE EWC, MOP SINK, AND
 HUB DRAIN- SECTION 901.2.1 FBC P.
  
 12) P3.2: PROVIDE TRAP SEAL PROTECTIONS FOR THE HUB
 DRAIN AND FLOOR DRAINS- SECTION 1002.4.1 FBC P.
  
 13) P0.1 & P3.2: REFER TO THE LEGEND AND PROVIDE THE
 CORRECT LINE SYMBOLS FOR THE CW, HW, & HWR LINES ON THE
 FLOOR PLAN DRAWING AND THE RISER- SECTION 107.2.1 WPB.
 PLEASE SEE COMMENT #4 AND CORRECT THE HWR CONNECTION
 LOCATION. PLEASE CLARIFY IF THERE IS A HW LINE RUNNING
 TO LAV-3- SECTION 107.2.1 WPB.
  
 14) P3.2: INDICATE HOW TEMPERED WATER WILL BE PROVIDED
 TO THE PUBLIC LAVATORIES- SECTION 419.5 FBC P.
  
 15) P3.2: PROVIDE A BACKFLOW PREVENTER FOR THE WATER
 SUPPLY LINE TO THE ICE MAKER BOX- SECTION 608.3 FBC P.
  
 16) P0.1: PROVIDE WATER SUPPLY AND SANITARY DRAIN AND
 VENT PIPING SPECIFICATIONS- SECTIONS 605 AND 702 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  