Plan Review Notes
Plan Review Notes For Permit 21080871
Permit Number 21080871
Review Stop P
Sequence Number 1
Notes
Date Text
2021-10-13 11:56:171ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21080871
 10/13/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) T1-0 CODE DATA: PROVIDE ON THE PLAN A LIST OF
 CURRENT FLORIDA CODES AND STANDARDS USED IN THE DESIGN
 OF THE PROJECT. PLEASE NOTE THAT ALTERATIONS TO PUBLIC
 SPACES AND BATHROOMS SHALL BE IN COMPLIANCE WITH THE
 FBC-2020 7TH EDITION ACCESSIBILITY CODE. ALTERATIONS TO
 DWELLING UNITS IN MULTI-FAMILY BUILDINGS CONSTRUCTED
 UNDER THE FAIR HOUSING ACT DESIGN MANUAL SHALL BE IN
 COMPLIANCE WITH THE DESIGN MANUAL. IN THIS CASE THE
 BUILDING WAS CONSTRUCTED IN 1972 WHICH PRECEDED THE
 MARCH 13, 1991 DATE WHEN THE FHDA CONSTRUCTION
 REQUIREMENTS FOR MULTIFAMILY BUILDINGS WENT INTO
 EFFECT. THE CURRENT PLANS PROVIDE NO INFORMATION OR
 GUIDANCE AS TO WHICH CODES SHOULD BE APPLIED. BASED ON
 THE DRAWINGS THE ALTERATIONS TO THE DWELLING UNITS WILL
 BE REVIEWED USING THE FAIR HOUSING DESIGN ACT MANUAL.
  
 2) T1-0: PLEASE PROVIDE A NUMBERED MASTER LIST OF
 DWELLING UNITS PER FLOOR THAT ARE BEING RENOVATED FOR
 INCREASED ACCESSIBILITY. PLEASE NUMBER EACH OF THE
 APARTMENTS ON THE PLUMBING OR ARCHITECTURAL FLOOR PLAN
 DRAWINGS SO THEY CORRELATE WITH THE LIST AND CLARIFY
 HOW THE NUMBER OF APARTMENTS WERE DETERMINED- ACCORDING
 TO WHICH STANDARD OR WHICH SECTION OF THE FAIR HOUSING
 DESIGN ACT MANUAL.
  
 3) T1-0: PLEASE REFER TO PAGE 7 OF THE INTRODUCTION TO
 THE FAIR HOUSING DESIGN ACT MANUAL: THE DESIGN
 PROFESSIONAL OF RECORD SHALL INDICATE ON THE PLANS
 WHICH OF THE TWO BATHROOM TYPES IS THE BASIS OF DESIGN-
 SPECIFICATION TYPE A OR B ON THE PLANS. PLEASE REFER TO
 PAGES 7.34- 7.39 OF THE DESIGN MANUAL FOR EXPLANATORY
 INFORMATION ON SPECIFICATION A & B AND SHOW COMPLIANCE.
 A COMPLETE AND ACCURATE REVIEW OF THE PROJECT CANNOT BE
 COMPLETED WITHOUT THE TYPE A OR B DESIGNATION.
  
 4) A0.3, A0.4, A1.1, A1.2: AS NOTED IN COMMENT #3 ABOVE
 PLEASE DESIGNATE TYPE A OR B AS THE BASIS OF DESIGN ON
 THE FLOOR PLANS.
  
 5) A1.1 & A1.2: PROVIDE THE DIMENSIONS OF THE CLEAR
 FLOOR SPACE DIAGRAMS SHOWN ON THE PLANS IN FOR THE
 KITCHEN SINKS AND APPLIANCES, WATER CLOSETS, LAVATORIES
 AND VANITIES, BATHTUBS, AND SHOWERS- SEE PAGES 7.1-
 7.59 OF THE MANUAL.
 PAGES 7.1- 7.30: CLEAR FLOOR SPACES FOR SINKS AND
 APPLIANCES
 PAGES 7.1- 7.30: CLEARANCES BETWEEN KITCHEN COUNTERS
 AND ALL OPPOSING ELEMENTS.
 PAGES 7.12- 7.16: REMOVABLE SINK AND APPLIANCE CABINET
 DOORS INCLUDING KNEE SPACES.
 PAGES 7.40-7.46: WATER CLOSET CLEAR FLOOR SPACES AND
 GRAB BAR LOCATIONS
 PAGES 7.47- 7.52: LAVATORY AND VANITY CLEAR FLOOR AND
 KNEE AND TOE CLEARANCES.
 PAGES 7.53- 7.55: BATHTUB CLEAR FLOOR SPACE AND CONTROL
 LOCATIONS
 PAGES 7.56- 7.59: SHOWER CLEAR FLOOR SPACES AND CONTROL
 LOCATIONS.
  
 6) A1.1 & A1.2: BASED ON THE LOCATIONS OF THE LAVATORY
 SINKS BY THE BATHTUB, IT APPEARS THAT SPECIFICATION
 TYPE A HAS BEEN SELECTED FOR THE BATHROOMS. PLEASE
 REFER TO PAGE 7.53- SPECIFICATION A- DIAGRAM 1 AND
 CONFIRM THIS IS THE CHOSEN DESIGN. PROVIDE THE
 DIMENSIONS OF THE CLEAR FLOOR SPACE DIAGRAMS AT THE
 BATHTUB AND LAVATORIES.
  
 7) A7.1: REFER TO COMMENT #1 AND PROVIDE CODE
 COMPLIANCE DATA NOTES ON THE PLAN- SECTION 107.2.1 WPB.
 IT APPEARS SOME OF THE DETAILS ON THE SHEET ARE DERIVED
 FROM ICC/ANSI A117.1-2003, AND SOME FROM THE FAIR
 HOUSING DESIGN ACT MANUAL.
  
 8) A7.1: THE TYPICAL LAVATORY DETAIL DOES NOT PROVIDE
 THE MAXIMUM 19-INCH EXTENSION OF THE CLEAR FLOOR SPACE
 UNDER THE LAVATORY- PAGE 7.52 FAIR HOUSING DESIGN ACT
 MANUAL.
  
 9) A7.1: PLEASE PROVIDE THE HEIGHTS OF THE TOILET SEATS
 FROM THE FINISHED FLOORS- PAGE 7.60 FHDA.
  
 10) A7.1- ELEV. 7 & 16: SHOW THE 27-INCH MINIMUM KNEE
 SPACE AT THE SINK- PAGE- 7.52 FHDA.
  
 11) A7.1 ELEV. 4, 5, 11, 12, 20: IT APPEARS THE
 ACCESSIBLE BATHTUB MAY BE DESIGNED IN ACCORDANCE WITH
 THE ICC/ANSI A117.1-2003. BASED ON THE ANSI STANDARD IT
 APPEARS THE GRAB BARS SHOWN IN THE DETAIL ARE NOT IN
 COMPLIANCE WITH SECTION AND FIGURE 607.4.1(A) FOR
 LENGTH AND SPACING FROM THE HEAD WALL. REFER TO FIG.
 607.4.1(B) AND PROVIDE THE CONTROL WALL GRAB BAR
 INSTALLATION DETAIL.
  
 12) A7.1 REFER TO SECTIONS 607.3 AND 610.2 ICC/ANSI
 A117.1-2003 AND PROVIDE BATHTUB SEAT DIMENSIONS AND
 MOUNTING HEIGHTS.
  
 13) A7.1 ELEV. 8, 9, 10, 19: REFER TO FIGURES 608.3.2 &
 608.5.2 AND PROVIDE THE ACCESSIBLE SHOWER GRAB BAR
 INSTALLATION LENGTHS, SPACES AND MOUNTING HEIGHTS.
  
 14) A7.1 ELEV. 8, 11, 13, 19, 20: REFER TO FIG. 604.5.1
 & 604.5.2 AND SHOW THE CORRECT LENGTHS AND SPACINGS OF
 THE WATER CLOSET GRAB BARS.
  
 15) P0.1: PROVIDE THE EFFICIENCY RATINGS OF THE
 TANKLESS WATER HEATERS AND SUBMIT MANUFACTURER'S
 SPECIFICATIONS- TABLE C404.2 FBC EC.
  
 16) P0.1 & P0.2: PROVIDE HW PIPE INSULATION
 SPECIFICATIONS- TABLE C403.2.10 FBC EC.
  
 17) P1.1: SHOW THE 6-INCH BUILDING DRAIN POINT OF
 CONNECT TO THE MAIN SEWER. IF SHOWN ON A CIVIL PLAN,
 PLEASE PROVIDE THE SHEET- SECTION 107.2.1 WPB.
  
 18) P1.1: PLEASE PROVIDE AN ENLARGED PIPING
 INSTALLATION DRAWING FOR THE LINT TRAP AND SUBMIT
 MANUFACTURER'S SPECIFICATIONS- SECTION 1003.6 FBC P.
 THE LOCATION AND CAPACITY OF THE INTERCEPTOR SHALL BE
 IN ACCORDANCE WITH MANUFACTURER?S SPECIFICATIONS AND
 INSTALLATION GUIDELINES.
  
 19) P2.3: THE KITCHEN SINK (SINK 1) DRAIN PIPES SHALL
 NOT CONNECT INTO THE WET VENT FOR THE BATHROOMS. THE
 DRAIN SHALL CONNECT DOWNSTREAM OF THE TUB FIXTURE DRAIN
 CONNECTION- SECTION 912.1 FBC P.
  
 20) P1.1 & P2.1: SHOW THE CW RISER LOCATIONS- SECTION
 107.2.1 WPB.
  
 21) P2.3: SHOW REQUIRED SHUTOFF VALVES FOR THE CW DOWN
 FEED PIPES SHOWN IN THE RISERS- SECTION 606 FBC P.
  
 22) P1.2 & P2.4: SHOW HW AND HWR LINES RUNS FROM THE
 STORAGE ROOM TO THE LINES RUNNING ABOVE THE CORRIDOR
 CEILING- SECTION 607.1 FBC P.
  
 23) P2.3: SHOW THE HW LINE CONNECTIONS TO THE SOURCES
 OF THE HOT WATER- SECTION 607.1 FBC P.
  
 24) P0.2: WH-3 & WH-4 APPEAR TO MISSING THE HWR
 CONNECTIONS- SECTION 607.2 FBC P.
  
 25) P0.1 P2.4: PROVIDE TRAP SEAL PROTECTION FOR THE
 FLOOR SINK IN THE WH STORAGE ROOM- SECTION 1002.4 FBC
 P.
  
 26) PROVIDE A SHOWER PAN DETAIL IN COMPLIANCE WITH-
 SECTION 421.5.2 FBC P. SHOW THE TYPE OF LINER TO BE
 INSTALLED AND SLOPE OF THE LINER.
  
 27) RELOCATING THE SHOWER DRAIN OUTLETS WILL REQUIRE
 THE FLOOR TO BE X-RAYED TO IN ORDER TO LOCATE
 REINFORCING STEEL OR POST STRESSED FLOOR TENDONS.
 PLEASE PLACE A NOTE ON THE PLANS TO VERIFY COMPLIANCE
 WILL BE MET- SECTION 107.2.1 WPB.
  
 28) NEW DRAIN PIPE PENETRATIONS OF THE EXISTING SLAB
 WILL REQUIRE FIRESTOPPING TO SEAL THE ANNULAR SPACE
 AROUND THE PIPING. PROVIDE A UL TESTED AND APPROVED
 FIRESTOPPING ASSEMBLY DETAIL ON THE PLAN- SECTION
 714.4.1.2 FBC B.
  
 29) SHEET L-5: THE IRRIGATION PLANS ARE PROVIDING NOTES
 ONLY AND NO ALTERATION DRAWINGS AND DETAILS. PROVIDE
 COMPLETE PLANS AND DETAILS INCLUDING LOCATIONS OF NEW
 AND ALTERED PIPING AND CONTROLS, AND INCLUDE EQUIPMENT
 SCHEDULES- SECTION 107.2.1 WPB. PLEASE NOTE THAT
 IRRIGATION CAN BE DEFERRED AND SUBMITTED UNDER A
 SEPARATE PERMIT. RELOCATION OF THE EXISTING BACKFLOW
 PREVENTER OR NEW BF PREVENTER INSTALLATION SHALL BE
 DONE UNDER SEPARATE PERMIT. N ADDITIONAL SEPARATE
 PERMIT- SECTIONS 105.1 & 107.1 WPB, AND SECTION D. WPB
 MANUAL FOR CROSS-CONNECTION CONTROL.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  