2021-09-16 15:53:45THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET S 2.2 - THERE IS AN INDICATION OF A PORTE
 COCHERE WITH A CLEARANCE HEIGHT OF 12'0".
  
 THE REQUIRED HEIGHT OF A FIRE LANE IS 13'6".
  
 AS THE SITE EMERGENCY VEHICLE TRAVEL PATH REQUIRES
 NAVIGATION OF THIS LOW HEIGHT STRUCTURE APPLICABLE
 WARNING SIGNAGE IS NEEDED TO DIRECT TRAFFIC AROUND. NO
 PARKING/FIRE LANE INDICATORS NEED TO BE PLACED AT THE
 GO AROUND LANE TO ENSURE NO PARKING.
  
 ADDITIONALLY, RAISING THE HEIGHT TO 13'6" WOULD ALLOW
 RESCUE VEHICLES TO USE THIS STRUCTURE FOR EMS TRANSPORT
 IN STORMY WEATHER.
  
 PLEASE REVIEW AND PROVIDE DETAILS FOR COMPLIANCE.
  
 2) THERE ARE NO INDICATIONS IF THE BUILDING/ROOMS WILL
 REMIAN OCCUPIED DURING CONSTRUCTION AND WHAT LIFE
 SAFETY MEASURES WILL BE PUT IN PLACE TO MAINTAIN
 REQUIRED EXIT TRAVEL PATHS AND EXIT DISCHARGE.
  
 PLEASE PROVIDE DETAILS.
  
  
 2A) THERE ARE NO INDCATIONS OF FIRE ALARM OR FIRE
 SPRINKLER WORK.
  
 IF APPLICABLE, ALL FIRE SPRINKLER & FIRE ALARM WORK.
 INCLUDING DEMO, SHALL BE DONE UNDER SEPARATE PERMITS &
 SHOP DRAWINGS.
  
 PLEASE PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGEMENT
  
  
 3) THERE ARE INDICATIONS OF BBQ AREAS AT THE PAVILLION.
  
 PLEASE PROVIDE WHAT TYPE OF BBQ, FUEL SOURCE, FUEL
 STORAGE AREA, FIRE EXTINQUISHER LOCATIONS.
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL