| 2021-11-19 16:47:03 | 2ND REVIEW FBC-2020 FUEL GAS |
| | PERMIT- 21080869 |
| | 11/19/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE |
| | 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTES IN |
| | CAP LETTERS. |
| | |
| | 1) FAILED 1F. SHEET P2.4: PROVIDE A COMPLETE GAS RISER |
| | DRAWING THAT INCLUDES ALL NEW AND EXISTING GAS PIPING |
| | AND APPLIANCES IN THE BUILDING- SECTIONS 401.3 & 401.4 |
| | FBC FG. THE CURRENT SHOWS ONLY PIPING TO THE DRYERS. |
| | REFER TO SECTIONS 402.1, 402.2 & 402.3 FBC FG. THE |
| | RISER SHALL INDICATE: |
| | F) FAILED. BRANCH AND CUT PIPE LENGTH MEASUREMENTS. |
| | PLEASE PROVIDE THE INDIVIDUAL LOW PRESSURE BRANCH PIPE |
| | LENGTHS AND THE TOTAL LOW PRESSURE PIPING RUN. |
| | |
| | 8) FAILED. P2.4: PROVIDE COMBUSTION AIR CALCULATIONS |
| | FOR THE GAS-FIRED DRYERS AND INDICATE HOW THE AIR WILL |
| | BE PROVIDED- SECTION 304.1 FBC FG. PLEASE PROVIDE THE |
| | COMBUSATION AIR CALCULATIONS ON THE PLAN. |
| | |
| | 9) FAILED. P2.4: PROVIDE A GAS DRYER EXHAUST DIAGRAM |
| | INDICATING THE TYPE AND SIZE OF EXHAUST DUCTS, TOTAL |
| | RUN LENGTH OF THE SYSTEM, AND TERMINATION LOCATION- |
| | SECTION 614.1 FBC FG. SHOW THE LOCATION OF REQUIRED |
| | CLEANOUTS- 614.3 AND PROVIDE TERMINATION CAP DETAILS- |
| | 614.4 FBC FG. NOT PROVIDED. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |