| Plan Review Notes For Permit 21080869 |
| Permit Number |
21080869 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-10-08 11:19:27 | 1ST REVIEW FBC-2020 MECHANICAL | | | PERMIT-21080869 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE PROVIDE THE ENTIRE COMCHECK DOCUMENTS FROM | | | THE MECHANICAL SYSTEMS. FBC EC C403.2.1 | | | | | | 2) PLEASE SHOW HOW YOU WILL PROVIDE THE REQUIRED | | | OUTDOOR VENTILATION. FBC M 402 & 403 | | | | | | 3) PLEASE SHOW THE OUTDOOR AIR CALCULATIONS FOR THE | | | BUSINESS AND COMMON AREAS. FBC M 403.3.1.1 AND TABLE | | | 403.3.1.1 | | | | | | 4) PLEASE PROVIDE THE SPECIFICATIONS FOR THE KITCHEN | | | HOODS WITH THE FIRE SUPPRESSING SYSTEM. FBC 107.2.1 | | | | | | | | | 5) ARE THE DRYER DUCTS IN THE LAUNDRY GOING TO BE | | | REPLACED? | | | | | | 6) IF THE CLOTHES DRYERS ARE TO BE NEW PLEASE PROVIDE | | | THE SPECIFICATIONS FOR THE COMMERCIAL DRYERS. | | | | | | 7) SHEET M1.1: PLEASE SHOW THE OUTDOOR AIR DUCTWORK FOR | | | THE AH-1. FBC M 403 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|