| Notes |
| Date |
Text |
| 2022-10-19 11:09:46 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) IN ADDITION TO THE CLEAN SIGNED AND SEALED DRAWINGS | | | THAT WERE SUBMITTED, PLEASE SUBMIT ANOTHER SET OF THE | | | POST TENSION DRAWINGS THAT HAVE BEEN REVIEWED BY THE | | | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE WITH A | | | NOTATION THAT THEY ARE FOUND TO BE IN GENERAL | | | CONFORMANCE TO THE DESIGN OF THE BUILDING. FBC | | | 107.3.4.1 | | | |
|