Plan Review Notes
Plan Review Notes For Permit 21080806
Permit Number 21080806
Review Stop B
Sequence Number 2
Notes
Date Text
2021-11-22 13:26:20BUILDING PLAN REVIEW
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 2ND REVIEW
  
 NOTICE: A SEPERATE ROOFING PERMIT IS REQUIRED. SEE
 PROVISO ON PLAN PAGE A102.
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 ADDRESS COMMENTS FROM 1ST REVIEW:
  
  
 3.PROVIDE A SOILS REPORT.
 R401.4 SOIL TESTS.
 WHERE QUANTIFIABLE DATA CREATED BY ACCEPTED SOIL
 SCIENCE METHODOLOGIES INDICATE EXPANSIVE, COMPRESSIBLE,
 SHIFTING OR OTHER QUESTIONABLE SOIL CHARACTERISTICS ARE
 LIKELY TO BE PRESENT, THE BUILDING OFFICIAL SHALL
 DETERMINE WHETHER TO REQUIRE A SOIL TEST TO DETERMINE
 THE SOIL?S CHARACTERISTICS AT A PARTICULAR LOCATION.
 THIS TEST SHALL BE DONE BY AN APPROVED AGENCY USING AN
 APPROVED METHOD.
 1803.2 INVESTIGATIONS REQUIRED.
 GEOTECHNICAL INVESTIGATIONS SHALL BE CONDUCTED IN
 ACCORDANCE WITH SECTIONS 1803.3 THROUGH 1803.5.
 WHERE REQUIRED BY THE BUILDING OFFICIAL OR WHERE
 GEOTECHNICAL INVESTIGATIONS INVOLVE IN-SITU TESTING,
 LABORATORY TESTING OR ENGINEERING CALCULATIONS, SUCH
 INVESTIGATIONS SHALL BE CONDUCTED BY A REGISTERED
 DESIGN PROFESSIONAL.
  
 NOTICE:
 BASED ON THE OFFICIAL ZONING MAP REFERRED TO IN SECTION
 53-2 OF CHAPTER 53 OF THE CITY CODE OF WEST PALM BEACH,
 FLORIDA, 1962, ADOPTED JUNE 15, 1964, YOUR PROPERTY,
 LOCATED AT 4210 WASHINGTON RD., W.P.B., FL, IS LOCATED
 IN AN AREA OF QUESTIONABLE SOILS AND REQUIRES
 INVESTIGATION BY A GEOTECHNICAL ENGINEER WITH ITS
 SUBSEQUENT SOILS REPORT AND DENSITY TESTING.
 THIS ONLY RELIEVES YOU FROM THE STATUTORY REQUIREMENTS
 OF THE FLORIDA BUILDING CODE. THERE MAY BE OTHER
 ENTITIES, SUCH AS YOUR DESIGN PROFESSIONAL OR YOUR
 LENDING INSTITUTION THAT MAY REQUIRE THE ABOVE
 MENTIONED INVESTIGATION.
  
  
 5.UNDER-FLOOR CRAWL SPACE SHALL COMPLY WITH R408: HOW
 WILL THIS BE ADDRESSED? PROVIDE A DETAIL OR NARRATIVE.
 5A) R408.1VENTILATION
 5B) R408.2 OPENINGS FOR UNDER-FLOOR VENTILATION.
 5C) R408.3 UNVENTED CRAWL SPACE.
 5D) R408.4 ACCESS.
  
 NEW COMMENT:
  
 6. PROVIDE PRODUCT APPROVALS FOR NEW WINDOW MULLIONS.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 PLEASE UPLOAD YOUR DOCUMENTS TO PROJECT DOX.
 DO NOT E-MAIL THEM TO THE PLANS EXAMINER.
  
  