| Plan Review Notes For Permit 21080792 |
| Permit Number |
21080792 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-08-24 09:34:46 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) THERE ARE INDICATIONS OF REMOVING THE ELEVATOR LOBBY | | | DOORS WITHOUT A RE-INSTALLATION OF THESE DOORS. | | | | | | ELEVATOR LOBBIES ARE REQUIRED WHERE DESIGNED UNDER THE | | | ORIGINAL EOR WHERE THE ELEVATOR SHAFT IS NOT | | | PRESSURIZED. | | | | | | PLEASE REVIEW THE ORIGINAL EOR'S LIFE SAFETY | | | REQUIREMENTS AND ENSURE THIS ELEVATOR LOBBY IS NOT | | | REQUIRED TO HAVE DOORS. | | | | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|