Plan Review Notes
Plan Review Notes For Permit 21080786
Permit Number 21080786
Review Stop P
Sequence Number 1
Notes
Date Text
2021-09-22 11:19:331ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21080786
 9/22/21
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET AN-2-1 & A-7-1: PLEASE PROVIDE SITE SPECIFIC
 ACCESSIBILITY DETAILS PER THE FBC ACC. MISSING FROM THE
 DRAWINGS ON A-7-1:
 A) CLEAR FLOOR SPACE DIMENSIONS FOR THE WATER CLOSETS-
 SECTION 604.3.
 B) CLEAR FLOOR SPACE DIMENSIONS FOR THE LAVATORIES-
 SECTION 606.2.
 C) TURNING SPACE DIAMETERS- SECTION 304.3.
 D) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4,
 FIGURES 604.5.1 & 604.5.2.
 E) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION
 606.2 & FIGURES 306.2 & 306.3.
 F) HEIGHT OF THE ACCESSIBLE URINAL RIM FROM THE
 FINISHED FLOOR- SECTION 605.2.
 G) CLEAR FLOOR SPACE DIMENSIONS FOR THE ACCESSIBLE
 URINAL- SECTION 605.2.
  
 2) SHEET A-7-2 DETAIL 3: THE RIM OF THE NEW SINK
 APPEARS TO BE ABOVE THE MAXIMUM 34-INCH HEIGHT FORM THE
 FINISH FLOOR- SECTION 606.3 FBC ACC.
  
 3) A-7-2 & A-7-4: : SHOW THE HEIGHTS OF THE EQUIPMENT
 CONTROLS FROM THE FINISH FLOORS AND REACH RANGES AS
 DETAILED IN SECTIONS 308.1- 308.3 FBC ACC.
  
 4) P-0.0: PROVIDE PLUMBING FIXTURE CALCULATIONS FOR THE
 NEW TENANT BUILD-OUT IN ACCORDANCE WITH TABLE 403.1 FBC
 P. PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED NUMBER OF FIXTURES.
  
 5) P0.0: THE DUAL-OUTLET STOP VALVE DOES NOT MEET
 COMPLIANCE AS THE REQUIRED FULL-OPEN TYPE SHUTOFF VALVE
 REQUIRED FOR THE WATER HEATERS AT THE LAVATORIES-
 SECTION 503.1 & 606.1(8) FBC P.
  
 6) P0.0 & P1.0: COLD OR TEMPERED WATER SHALL BE
 DELIVERED FROM THE LAVATORIES- SECTION 419.5 FBC P. THE
 PLAN IS NOT IN COMPLIANCE.
  
 7) P1-0: IT APPEARS A FLOOR DRAIN IS MISSING AT THE ICE
 MAKER LOCATION- SECTION 107.2.1 WPB.
  
 8) P1-0: THE URINAL DRAINS SHALL CONNECT TO THE 3-INCH
 SANITARY AT A POINT DOWNSTREAM OF THE HORIZONTAL WET
 VENT FOR THE MEN'S BATHROOM GROUP- SECTION 912.1 FBC P.
 A COMMON VENT WILL BE REQUIRED FOR THE URINALS- SECTION
 911.1.
  
 9) P1-0: SHOW LOCATIONS OF WATER HAMMER ARRESTORS WHERE
 REQUIRED- SECTION 604.9 FBC P.
  
 10) P1-0: CLARIFY THE LOCATIONS OF REQUIRED BACKFLOW
 PREVENTERS FOR SUPPLY LINES TO THE DISHWASHER, ICE
 MAKER, COFFEE MAKER, WATER DISPENSERS ETC.- SECTION
 608.3 FBC P.
  
 11) P0.0 & P2.0: INDICATE THE MAKES AND MODELS OF THE
 PLUMBING FIXTURES IN THE SCHEDULE AND SUBMIT
 MANUFACTURER'S SPECIFICATIONS FOR THE WALL HUNG FLUSH
 TANK TOILET- SECTION 303.4 FBC P.
  
 12) P1.0 & P2.0: SHOW THE LOCATION OF THE REQUIRED
 ACCESS PANEL FOR THE FLUSH TANK IN THE WALL- SECTION
 425.3.4 FBC P.
  
 13) P0.0: PROVIDE EQUIPMENT SCHEDULES FOR EQ-2, 5, 6, &
 7 AND SUBMIT MANUFACTURER'S SPECIFICATIONS- SECTION
 303.4.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  