| 2021-09-03 06:15:11 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT-21080782 |
| | 9/3/2021 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC P- FLORIDA PLUMBING CODE SEVENTH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SEVENTH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE SEVENTH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE SEVENTH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE SEVENTH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SEVENTH |
| | EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SEVENTH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SEVENTH |
| | EDITION 2020 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1- ON PAGE 6.1 ALL CORRECT PLUMBING DWV PIPE SIZES |
| | SHALL BE INDICATED ON EACH SECTION OF PIPE. 3" IS THE |
| | MINIMUM PIPE SIZE FOR A WATER CLOSET DRAIN LINE, THE |
| | PLAN INDICATES 2". WPB AMENDMENTS TO THE FBC |
| | SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | 2- THE PLAN INDICATESTHE TANKLESS WATER HEATER IS GOING |
| | TO BE INSTALLED OUTDOORS, PLEASE PROVIDE THE |
| | MANUFACTURES SPECIFICATIONS CLEARLY INDICATING THE |
| | ELECTRIC TANKLESS WATER HEATER IS RATED FOR THE |
| | INSTALLATION OUTDOORS.WPB AMENDMENTS TO THE FBC |
| | SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |