Plan Review Notes
Plan Review Notes For Permit 21080730
Permit Number 21080730
Review Stop R
Sequence Number 2
Notes
Date Text
2022-01-11 11:14:12SECOND ROOFING REVIEW:
  
 1-PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL
 PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL):
  
 A)HIP & RIDGE METAL SUPPORT TO BE USED. AND, CLEARLY
 MARK SPECIFIC METAL CHANNEL TO BE INSTALLED. SEE
 PERFORMANCE LIMITATIONS TABLES ON PRODUCT APPROVAL
 SUBMITTED.
  
 RESPONSE:
 NOT SUBMITTED.
  
 B) ROOF UNDERLAYMENT FL14317-R12 SUBMITTED: CLEARLY
 MARK WHICH TESTED ASSEMBLY IS GOING TO BE INSTALLED.
 SEC. 5.8.2 AND SEC. 5.8.3 OF PRODUCT APPROVAL
 SUBMITTED.
 THERE ARE 6 ASSEMBLIES. SPECIFY WHICH ASSEMBLY FROM
 SEC. 5.8.3.1 IS GOING TO BE INSTALLED.
  
 RESPONSE:
 STILL NOT CLEAR WHICH ASSEMBLY TO BE USED. TABLE 2 ON
 PAGE 4 OF 6 OF PRODUCT APPROVAL WAS MARKED, BUT IT
 DOESN'T CLARIFY IF USING ASTM D226 TYPE II FELT OR
 CITADEL PLUS AS THE SUBSTRATE. I F USING ASTM D226 FELT
 , THEN PROVIDE FRSA/TRI PRESCRIPTIVE METHOD USED. IF
 USING CITADEL PLUS , THEN CIRCLE WHICH ASSEMBLY IS
 GOING TO BE USED. SEE SEC. 5.8.2 OF PRODUCT APPROVAL
 SUBMITTED.
  
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  